Inspection Detail
Inspection: 14631121 - Hegemann Electric Inc
Inspection Information - Office: Arizona Division Of Occupational Safety And Health (Adosh)
Site Address:
Hegemann Electric Inc
180 West Broadway
Tucson, AZ 85701
Mailing Address:
1665 East 18th St Suite 119, Tucson, AZ 85719
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 06/29/1984
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 06/29/1984
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360578447 |
Investigation Summary
Two employees were installing new compression-type connectors on conductors on the load side of an electrical switchboard. The switchboard contained a three-phase circuit operating at 480 volts (277 volts to ground), 1200 amperes. The fuses for the circuit had been removed, deenergizing the load side of the circuit. Employee #2 was tightening one of the connectors when the supply side of the circuit faulted to ground or from one phase to another. (Employee #1 was standing beside employee #2, in front of the switchboard.) No defects that could have caused the fault were found in the switchboard. A pair of pliers and a screwdriver were lying in the bottom of the switchboard. It was theorized that employee #1 may have attempted to remove them while employee #2 was installing the connectors and, in the process, may have accidentally struck the uninsulated portion of the circuit on the energized side. Both employees received second- and third-degree burns from the ensuing electric arc and were hospitalized.
Keywords: BURN, CLOTHING, E GI II, ELECTRIC ARC, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, ELECTRICAL FAULT, HAND TOOL
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 14631121 | Hospitalized injury | Burn/Scald(Heat) | Electricians | ||
| 2 | 14631121 | Hospitalized injury | Burn/Scald(Heat) | Electricians |