Case Status: CLOSED

Inspection: 1457377.015 - Harper Limbach Llc

Inspection Information - Office: Tampa Area Office

 

Inspection Nr: 1457377.015
Report ID: 0420600
Date Opened: 01/13/2020

Site Address:
Harper Limbach Llc
11375 Cortez Blvd.
Spring Hill, FL 34613

Mailing Address:
5102 W Laurel Street, Ste 800, Tampa, FL 33607

Union Status: NonUnion

SIC:

NAICS: 238220/ Plumbing, Heating, and Air-Conditioning Contractors


Inspection Type: Referral

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 01/13/2020

Emphasis:

Case Closed: 12/02/2020


Related Activity
Type Activity Nr Safety Health
Referral 1527708 Yes
Inspection 1462471 Yes
Case Status: CLOSED
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $5,783 $0 $0 $0 $0 $5,783
Current Penalty $0 $0 $0 $5,783 $0 $5,783
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 19260021 B02 04/29/2020 $5,783 $5,783 $0 06/03/2020 F - Formal Settlement  

Investigation Summary

Investigation Nr: 123344.015
Event: 12/17/2019
Employee sustains burns when valve fails and pipe bursts

At 11:30 a.m. on December 17, 2019, an employee working as a pipefitter for a plumbing and HVAC contractor was installing piping at a new facility. The employee was checking the system for leaks. The employee was working with coworkers flushing the new system with water using PVC pipe rated for 130 degrees Fahrenheit. At the same time, water in the steam portion of the system was being brought up to temperatures ranging from 140 to 180 degrees Fahrenheit. As a result of a mis-wired electronic valve, steam heated the water in the part of the system being flushed and caused the PVC pipe to burst. When the piping came loose, the employee was sprayed with 180 degrees Fahrenheit water. The employee sustained second degree burns to his chest and knees and was hospitalized.

Keywords: Burn, Chest, Defect, High Temperature, Hot Water, Installing, Knee, Leak, Leg, Malfunction, Misjudgment, Misjudgment of Hazardous Situation, Pipe, Plumbing, Regulator Valve, Sprayed, Steam, Struck By, Testing, Water Pipe, Work Surface

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1457377.015 34 M Hospitalized injury Plumber, pipefitter and steamfiter apprentices
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.