Inspection Detail
Inspection: 14572390 - Homer Electric Assocs
Inspection Information - Office: Alaska Department Of Labor Osh Enforcement
Site Address:
Homer Electric Assocs
3977 Lake St
Homer, AK 99603
Mailing Address:
, , 00000
Union Status: Union
SIC:4911
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 04/17/1984
Emphasis:
Case Closed: 06/29/1984
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360577431 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 2 | 2 | ||||
Current Violations | 2 | 2 | ||||
Initial Penalty | $960 | $0 | $0 | $0 | $0 | $960 |
Current Penalty | $480 | $0 | $0 | $0 | $0 | $480 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 50220 A04 | 05/09/1984 | 05/12/1984 | $240 | $480 | $0 | I - Informal Settlement | ||
2. | 02001 | Serious | 50220 A04 | 05/09/1984 | 05/12/1984 | $240 | $480 | $0 | I - Informal Settlement |
Investigation Summary
A five-person crew was assigned to remove a three-phase switching cabinet. Two of the three phase conductors supplying this cabinet were to be abandoned, and the third phase was to be used for a new single-phase transformer. The transformer was to be installed at the site of the retired switching cabinet. The conductors in the energized switching cabinet were mismarked. Consequently, one of the employees disconnected the wrong conductors. Instead of disconnecting a load-side connection in the cabinet, he had disconnected a 14.4-kilovolt-to-ground power supply cable and had laid it alongside the cabinet. He then picked up the cable, which he believed to be deenergized. He received an electric shock and sustained burns to his left leg and both wrists. He was hospitalized for his injuries.
Keywords: BURN, E GI IV, ELECTRICAL, MARKING, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR, ELECTRIC SHOCK, ELECTRICAL CABINET
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 14572390 | Hospitalized injury | Electric Shock | Geologists and geodesists |