Inspection Detail
Inspection: 1451735.015 - Service Refrigeration, Llc
Inspection Information - Office: Houston North Area Office
Site Address:
Service Refrigeration, Llc
10777 Kuykendahl Road
The Woodlands, TX 77375
Mailing Address:
15800 International Plaza Drive Suite 100, Houston, TX 77032
Union Status: NonUnion
SIC:
NAICS: 238220/ Plumbing, Heating, and Air-Conditioning Contractors
Inspection Type: Referral
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 02/10/2020
Emphasis:
Case Closed: 03/26/2020
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Referral | 1527622 | Yes | |
| Inspection | 1451783 | Yes |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $8,675 | $0 | $0 | $0 | $0 | $8,675 |
| Current Penalty | $0 | $0 | $0 | $8,675 | $0 | $8,675 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 19260028 A | 02/11/2020 | 03/02/2020 | $8,675 | $8,675 | $0 | I - Informal Settlement |
Investigation Summary
At 4:00 p.m. on December 16, 2019, an employee working as an electrician for an HVAC and plumbing company was installing a circuit breaker switch. The employee was working on an energized 480-VAC electrical panel without wearing personal protective arc flash equipment. The employee was using a set of pliers to remove two bolts from the bus bar where the breaker was to be installed. While removing the second bolt, the pliers touched the energized bus bar creating an arc flash explosion. The employee suffered second degree burns to the face, neck and left arm and was hospitalized.
Keywords: Arm, Burn, Circuit Breaker, Contact, Electric Arc, Electric Arc Flash, Electrical Burn, Electrical Work, Electrical panel, Electrician, Energized, Face, Fire, HVAC, Hand Tool, Installing, Lockout, Lockout/Tagout, Misjudgment, Misjudgment of Hazardous Situation, Neck, PPE, PPE Hazard Assessment, Struck By
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 1451735.015 | 52 | M | Hospitalized injury | Electricians |