Inspection Detail
Inspection: 1442448.015 - Titan Modular Systems, Inc.
Inspection Information - Office: Savannah Area Office
Site Address:
Titan Modular Systems, Inc.
162 Industrial Drive
Alma, GA 31510
Mailing Address:
162 Industrial Drive, Alma, GA 31510
Union Status: NonUnion
SIC:
NAICS: 321991/Manufactured Home (Mobile Home) Manufacturing
Inspection Type: Referral
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 10/31/2019
Emphasis:
Case Closed: 07/30/2020
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Referral | 1513371 | Yes |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 3 | 3 | ||||
| Current Violations | 2 | 2 | ||||
| Initial Penalty | $32,445 | $0 | $0 | $0 | $0 | $32,445 |
| Current Penalty | $21,402 | $0 | $0 | $0 | $0 | $21,402 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001A | Serious | 19100303 E01 II | 04/22/2020 | 05/18/2020 | $11,859 | $13,359 | $0 | I - Informal Settlement | ||
| 2. | 01001B | Serious | 19100303 F01 | 04/22/2020 | 05/18/2020 | $0 | $0 | $0 | I - Informal Settlement | ||
| 3. | 01003A | Serious | 19100335 A01 I | 04/22/2020 | 05/18/2020 | $9,543 | $9,543 | $0 | I - Informal Settlement | ||
| 4. | 01003B | Serious | 19100335 A01 IV | 04/22/2020 | 05/18/2020 | $0 | $0 | $0 | I - Informal Settlement | ||
| 5. | 01003C | Serious | 19100335 A01 V | 04/22/2020 | 05/18/2020 | $0 | $0 | $0 | I - Informal Settlement | ||
| 6. | 01003D | Serious | 19100332 B01 | 04/22/2020 | 05/18/2020 | $0 | $9,543 | $0 | I - Informal Settlement |
Investigation Summary
At 9:00 a.m. on October 26, 2019, an employee and an electrical contractor turned off the power to switch #1 of 5 in the main power supply disconnect located in the power distribution area of the production plant. The employees thought the switch controlled a hot circuit for the air dryer disconnect and disconnect switch located in the air compressor room. The employee checked the voltage across the three leads inside disconnect switch #1 with a voltage meter and it read zero for all of the leads. While the employee was unscrewing the third lead inside of disconnect switch #1, the wire popped out and hit the Allen wrench that he was using, resulting in an arc flash. The employee was hospitalized to treat first degree burns to both hands, second degree burns to his left forearm, and mild burns to his neck.
Keywords: Contact, Electric Arc, Electric Arc Flash, Electric Switch, Electrical Burn, Electrical Wire, Electrical Work, Energized, Forearm, Hand, Neck, Wrench
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 1442448.015 | 51 | M | Hospitalized injury |
Translate