Powered by GoogleTranslate

Inspection Detail

Inspection: 1437102 - Toms Cabinets Inc

Inspection Information - Office: Dallas Area Office

 

Inspection Nr: 1437102
Report ID: 0626300
Date Opened: 05/02/1984

Site Address:
Toms Cabinets Inc
204 Sentry Dr
Mansfield, TX 76063

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:2434

NAICS: 0 


Inspection Type: Planned

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/29/1984

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 10/01/1985


Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1 2
Current Violations 1 1 2
Initial Penalty $200 $0 $0 $0 $0 $200
Current Penalty $200 $0 $0 $0 $0 $200
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100213 H03 06/08/1984 06/20/1984 $200 $200 $0 -  
2. 02001 Other 19100215 B09 06/08/1984 06/20/1984 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14400915
Event: 05/02/1984
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

A three-person power line crew was upgrading a 12-kilovolt overhead power line to a 34-kilovolt line. The employees were setting new utility poles and replacing the phase conductors. The crew had not installed rubber insulating line hose or blankets on the conductors. One of the employees on the crew was working from an aerial lift. This power line worker, who was not using rubber insulating gloves or sleeves, raised his bucket and contacted one of the 7500-volt-to-ground phase conductors. The employee was electrocuted.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1437102 Hospitalized injury Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.