Case Status: CLOSED

Inspection: 1434270.015 - City Of Santa Barbara, Waterfront Department

Inspection Information - Office: Van Nuys District Office

 

Inspection Nr: 1434270.015
Report ID: 0950643
Date Opened: 09/26/2019

Site Address:
City Of Santa Barbara, Waterfront Department
200 Stearns Warf
Santa Barbara, CA 93109

Mailing Address:
735 Anacapa Street P. O. Box 1990, Santa Barbara, CA 93102

Union Status: Union

SIC:

NAICS: 921190/Other General Government Support


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: LocalGovt

Safety/Health: Safety

Close Conference: 02/26/2020

Emphasis:

Case Closed: 08/10/2021


Related Activity
Type Activity Nr Safety Health
Accident 1495188
Case Status: CLOSED
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2 4
Current Violations 2 2 4
Initial Penalty $15,750 $0 $0 $560 $0 $16,310
Current Penalty $15,750 $0 $0 $560 $0 $16,310
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 3203(A) 02/26/2020 04/01/2020 $185 $185 $0 Z - Issued  
2. 01002 Other 24730001 A 02/26/2020 03/16/2020 $375 $375 $0 Z - Issued  
3. 02001 Serious 23200001 A 02/26/2020 $6,750 $6,750 $0 Z - Issued  
4. 03001 Serious 23200002 D 02/26/2020 $9,000 $9,000 $0 Z - Issued  

Investigation Summary

Investigation Nr: 120272.015
Event: 08/27/2019
Employee suffers burns due to live electrical panel

At 3:45 p.m. on August 27, 2019, an employee, a maintenance worker, was installing a latch lock at the base of an electrical panel so that it is accessible to only certain authorized personnel, not to the public. While installing the latch lock at the base of the electrical panel, the employee lifted the dead front cover to drill the third hole for the latch, because the dead front cover has a protruding stopper. While drilling the third hole for the third screw with a cordless hammer driver drill (Manufacturer: Makita, Model: XPH07), that third screw got stuck. Then, the employee put the drill in reverse, and when he hit the trigger, the drill swung back into the energized buss bar of the electrical panel, creating an electric arc and burning his right hand. The employee suffered from first and second degree burns on his right hand and was treated without hospitalization. Cal/OSHA identified several causal factors, including but not limited to: the supervisor was notified about the work task and did not ensure that it is safe to do so, employee was not qualified to work in proximity to live electrical systems, employee assumed that it is safe to install a latch lock and lift the dead front cover of the electrical panel. Employee suffered from first and second degree burns on his right hand. The employee exposed himself to the energy from electric arc derived from the live electrical components of the panel.

Keywords: Burn, Drill, Electric Arc, Electric Arc Flash, Electrical Box, Electrical Burn, Hand

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1434270.015 47 M Non Hospitalized injury Occupation Not Listed
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.