Inspection Detail
Inspection: 1426188.015 - Iowa State University
Inspection Information - Office: Iowa 0751910
Site Address:
Iowa State University
618 Bissell Rd
Ames, IA 50011
Mailing Address:
515 Morrill Road 3550 Beardshear Hall, Ames, IA 50011
Union Status: Union
SIC:
NAICS: 611310/ Colleges, Universities, and Professional Schools
Inspection Type: Referral
Scope: Partial
Advanced Notice: N
Ownership: StateGovt
Safety/Health: Safety
Close Conference: 08/26/2019
Emphasis:
Case Closed: 12/18/2019
Type | Activity Nr | Safety | Health |
---|---|---|---|
Referral | 1491204 | Yes |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 5 | 5 | ||||
Current Violations | 3 | 3 | ||||
Initial Penalty | $66,300 | $0 | $0 | $0 | $0 | $66,300 |
Current Penalty | $39,780 | $0 | $0 | $0 | $0 | $39,780 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19100269 M02 II | 10/30/2019 | 12/18/2019 | $13,260 | $13,260 | $0 | I - Informal Settlement | ||
2. | 01002A | Serious | 19100269 L04 I | 10/30/2019 | 12/18/2019 | $13,260 | $13,260 | $0 | I - Informal Settlement | ||
3. | 01002B | Serious | 19100269 L08 V | 10/30/2019 | 12/18/2019 | $0 | $13,260 | $0 | I - Informal Settlement | ||
4. | 01004 | Serious | 19100269 N02 | 10/30/2019 | 12/18/2019 | $13,260 | $13,260 | $0 | I - Informal Settlement | ||
5. | 01005 | Serious | 19100269 T03 IV | 10/30/2019 | 12/18/2019 | $0 | $13,260 | $0 | I - Informal Settlement | Citation has been deleted. |
Investigation Summary
At 1:15 p.m. on August 22, 2019, an employee was removing fuses from a 4,160-volt substation cabinet. As the employee was removing the canister fuses, his right arm came into contact with the feeder line and his left arm came into contact with the left side of the panel door. This created a circuit and caused the employee to become shocked. The employee suffered electrical shock, fractured ribs, fractured vertebrae, burns to both elbows, and cardiac arrest. The employee was hospitalized for treatment.
Keywords: Burn, Cardiac Arrest, Electric Shock, Electric current, Electrical, Electrical Burn, Electrical Cabinet, Electrical Work, Electrical panel, Fracture, Fuse, Rib, Shock, Substation, Vertebra
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 1426188.015 | 60 | M | Hospitalized injury | Electrical and electronic engineers |