Inspection: 1425149 - C. C. Teague & Son Construction Co., Inc.

Inspection Information - Office: Dallas Area Office

 

Inspection Nr: 1425149
Report ID: 0626300
Date Opened: 06/12/1986

Site Address:
C. C. Teague & Son Construction Co., Inc.
Inters. Of Arapahoe & Yale (Ne Corner)
Richardson, TX 75081

Mailing Address:
3249 E. Renner Road, Richardson, TX 75081

Union Status: NonUnion

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 06/13/1986

Emphasis:

Case Closed: 08/25/1986


Related Activity
Type Activity Nr Safety Health
Accident 360641203
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 3 3
Initial Penalty $1,190 $0 $0 $0 $0 $1,190
Current Penalty $1,190 $0 $0 $0 $0 $1,190
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260021 B02 08/04/1986 08/21/1986 $420 $420 $0 -  
2. 01002 Serious 19260556 A02 08/04/1986 08/11/1986 $490 $490 $0 -  
3. 01003 Serious 19260556 B02 V 08/04/1986 08/11/1986 $280 $280 $0 -  

Investigation Summary

Investigation Nr: 14400188
Event: 06/10/1986
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU AERIAL LIFT

AN EMPLOYEE WAS WORKING FROM AN INSULATED AERIAL LIFT OVER THREE PHASES OF A 7200-VOLT OVERHEAD POWER LINE. HE WAS WORKING ON ANOTHER DEENERGIZED, PARTIALLY GROUNDED LINE. HE HAD LOWERED THE AERIAL LIFT BETWEEN ONE OF THE OUTER LINES AND THE MIDDLE LINE. AN UNINSULATED PORTION OF THE UPPER PART OF THE BOOM CONTACTED THE MIDDLE PHASE CONDUCTOR. A CONDUCTIVE PATH WAS SET UP FROM THE CONDUCTOR TO THE BOOM, TO THE METAL-CLAD HYDRAULIC HOSES, TO THE HOSE CONNECTORS, AND TO THE WIRE USED TO HOLD BROKEN TOOL CONNECTORS TO THE SAFETY-BELT TIE-OFF RING INSIDE THE BUCKET OF THE AERIAL LIFT. ANOTHER WIRE, HOLDING A PAIR OF LARGE LINEMAN'S PLIERS (XPJ 53 NICOMPRESS TOOL), WAS TIED TO THE BUCKET AT THIS POINT. THE EMPLOYEE'S KNEE CONTACTED THE LINEMAN'S PLIERS WHILE HE WAS HOLDING THE GROUNDED CONDUCTOR, AND HE WAS ELECTROCUTED.

Keywords: OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1425149 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.