Inspection Detail
Inspection: 1425149 - C. C. Teague & Son Construction Co., Inc.
Inspection Information - Office: Dallas Area Office
Site Address:
C. C. Teague & Son Construction Co., Inc.
Inters. Of Arapahoe & Yale (Ne Corner)
Richardson, TX 75081
Mailing Address:
3249 E. Renner Road, Richardson, TX 75081
Union Status: NonUnion
SIC:1623
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: Y
Ownership: Private
Safety/Health: Safety
Close Conference: 06/13/1986
Emphasis:
Case Closed: 08/25/1986
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360641203 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 3 | 3 | ||||
| Current Violations | 3 | 3 | ||||
| Initial Penalty | $1,190 | $0 | $0 | $0 | $0 | $1,190 |
| Current Penalty | $1,190 | $0 | $0 | $0 | $0 | $1,190 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19260021 B02 | 08/04/1986 | 08/21/1986 | $420 | $420 | $0 | - | ||
| 2. | 01002 | Serious | 19260556 A02 | 08/04/1986 | 08/11/1986 | $490 | $490 | $0 | - | ||
| 3. | 01003 | Serious | 19260556 B02 V | 08/04/1986 | 08/11/1986 | $280 | $280 | $0 | - |
Investigation Summary
AN EMPLOYEE WAS WORKING FROM AN INSULATED AERIAL LIFT OVER THREE PHASES OF A 7200-VOLT OVERHEAD POWER LINE. HE WAS WORKING ON ANOTHER DEENERGIZED, PARTIALLY GROUNDED LINE. HE HAD LOWERED THE AERIAL LIFT BETWEEN ONE OF THE OUTER LINES AND THE MIDDLE LINE. AN UNINSULATED PORTION OF THE UPPER PART OF THE BOOM CONTACTED THE MIDDLE PHASE CONDUCTOR. A CONDUCTIVE PATH WAS SET UP FROM THE CONDUCTOR TO THE BOOM, TO THE METAL-CLAD HYDRAULIC HOSES, TO THE HOSE CONNECTORS, AND TO THE WIRE USED TO HOLD BROKEN TOOL CONNECTORS TO THE SAFETY-BELT TIE-OFF RING INSIDE THE BUCKET OF THE AERIAL LIFT. ANOTHER WIRE, HOLDING A PAIR OF LARGE LINEMAN'S PLIERS (XPJ 53 NICOMPRESS TOOL), WAS TIED TO THE BUCKET AT THIS POINT. THE EMPLOYEE'S KNEE CONTACTED THE LINEMAN'S PLIERS WHILE HE WAS HOLDING THE GROUNDED CONDUCTOR, AND HE WAS ELECTROCUTED.
Keywords: OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, AERIAL LIFT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 1425149 | Fatality | Electric Shock | Electrical power installers and repairers |