Inspection Detail
Inspection: 1419422.015 - Ameren Illinois
Inspection Information - Office: Peoria Area Office
Site Address:
Ameren Illinois
8420 N. University Street
Peoria, IL 61615
Mailing Address:
8420 N. University Street, Peoria, IL 61615
Union Status: Union
SIC:
NAICS: 221122/Electric Power Distribution
Inspection Type: Referral
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 07/31/2019
Emphasis:
Case Closed: 12/21/2020
Type | Activity Nr | Safety | Health |
---|---|---|---|
Referral | 1481838 | Yes |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 1 | ||||
Current Violations | 1 | 1 | ||||
Initial Penalty | $11,934 | $0 | $0 | $0 | $0 | $11,934 |
Current Penalty | $11,934 | $0 | $0 | $0 | $0 | $11,934 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001A | Serious | 19100269 M03 II | 12/09/2019 | 01/02/2020 | $11,934 | $11,934 | $0 | 01/07/2020 | F - Formal Settlement | |
2. | 01001B | Serious | 19100269 D06 | 12/09/2019 | 01/02/2020 | $0 | $0 | $0 | 01/07/2020 | F - Formal Settlement | Citation has been deleted. |
Investigation Summary
At 12:45 p.m. on July 29, 2019, an employee was preparing to remove an electrical lead from a bushing on a portable substation. The employer had added a maintenance breaker which allowed maintenance personnel to supply power to a motor that moved a tap changer. The maintenance breaker allowed an extension cord, used to maintain batteries and supply power to a heater, to back-feed electricity through the transformers and up to the bushing that the employee was touching. The maintenance breaker was not operated in a manner to control the energy to the equipment. The employee incurred an electrical shock and burns to his back and hands which required hospitalization.
Keywords: Back, Circuit Breaker, Contact, Electric Shock, Electrical, Electrical Burn, Electrician, Hand, Installing, Lockout, Lockout/Tagout, Maintenance, Misjudgment, Misjudgment of Hazardous Situation, Power Plant, Power Trans Appar, Shock, Substation, Transformer
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 1419422.015 | 38 | M | Hospitalized injury | Electrical power installers and repairers |