Case Status: CLOSED

Inspection: 1419422.015 - Ameren Illinois

Inspection Information - Office: Peoria Area Office

 

Inspection Nr: 1419422.015
Report ID: 0524500
Date Opened: 07/31/2019

Site Address:
Ameren Illinois
8420 N. University Street
Peoria, IL 61615

Mailing Address:
8420 N. University Street, Peoria, IL 61615

Union Status: Union

SIC:

NAICS: 221122/Electric Power Distribution


Inspection Type: Referral

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/31/2019

Emphasis:

Case Closed: 12/21/2020


Related Activity
Type Activity Nr Safety Health
Referral 1481838 Yes
Case Status: CLOSED
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $11,934 $0 $0 $0 $0 $11,934
Current Penalty $11,934 $0 $0 $0 $0 $11,934
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19100269 M03 II 12/09/2019 01/02/2020 $11,934 $11,934 $0 01/07/2020 F - Formal Settlement  
2. 01001B Serious 19100269 D06 12/09/2019 01/02/2020 $0 $0 $0 01/07/2020 F - Formal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 118464.015
Event: 07/29/2019
Employee incurs shock and burns from energized bushing

At 12:45 p.m. on July 29, 2019, an employee was preparing to remove an electrical lead from a bushing on a portable substation. The employer had added a maintenance breaker which allowed maintenance personnel to supply power to a motor that moved a tap changer. The maintenance breaker allowed an extension cord, used to maintain batteries and supply power to a heater, to back-feed electricity through the transformers and up to the bushing that the employee was touching. The maintenance breaker was not operated in a manner to control the energy to the equipment. The employee incurred an electrical shock and burns to his back and hands which required hospitalization.

Keywords: Back, Circuit Breaker, Contact, Electric Shock, Electrical, Electrical Burn, Electrician, Hand, Installing, Lockout, Lockout/Tagout, Maintenance, Misjudgment, Misjudgment of Hazardous Situation, Power Plant, Power Trans Appar, Shock, Substation, Transformer

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1419422.015 38 M Hospitalized injury Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.