Powered by GoogleTranslate

Inspection Detail

Inspection: 1412451 - Smackover Electric Co Inc

Inspection Information - Office: Little Rock Area Office

 

Inspection Nr: 1412451
Report ID: 0627100
Date Opened: 01/15/1985

Site Address:
Smackover Electric Co Inc
Phillips Oil Field 7 Miles East Of
Smackover, AR 71762

Mailing Address:
Po Box A, Smackover, AR 71762

Union Status: NonUnion

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 01/16/1985

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 01/16/1985


Related Activity
Type Activity Nr Safety Health
Accident 360576136

Investigation Summary

Investigation Nr: 14496186
Event: 01/12/1985
ELECTRIC SHOCK - CONTACT WITH LIVE PART THRU JUMPER

AN EMPLOYEE WAS ON A UTILITY POLE TO DISCONNECT PRIMARY PHASE CONDUCTORS. HE USED A HOT STICK TO REMOVE THE JUMPER CONDUCTORS FROM ALL THREE PHASE CONDUCTORS. ONE OF THE JUMPERS WAS STIFF AND REMAINED NEAR THE PRIMARY PHASE CONDUCTOR WHEN IT WAS DISCONNECTED. THE EMPLOYEE THEN STARTED TO REMOVE THE JUMPER CONDUCTORS FROM THEIR RESPECTIVE CUT-OUT SWITCHES. WHEN HE PULLED ON THE STIFF JUMPER, IT DROPPED BACK INTO CONTACT WITH THE PRIMARY PHASE CONDUCTOR. THE EMPLOYEE WAS ELECTROCUTED.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, ELECTROCUTED, E PTD, ELEC UTILITY WORK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1412451 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.