Powered by GoogleTranslate

Inspection Detail

Inspection: 1412436 - Brown & Root Inc

Inspection Information - Office: Little Rock Area Office

 

Inspection Nr: 1412436
Report ID: 0627100
Date Opened: 12/24/1984

Site Address:
Brown & Root Inc
Nekoosa Paper Mill Hwy 71n
Ashdown, AR 71822

Mailing Address:
P O Box 2787, Longview, TX 75606

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/26/1984

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 07/18/1986


Related Activity
Type Activity Nr Safety Health
Accident 360575930
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $640 $0 $0 $0 $0 $640
Current Penalty $640 $0 $0 $0 $0 $640
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260400 C01 03/08/1985 03/11/1985 $640 $640 $0 03/26/1985 R - Review Commission  
2. 01002 Serious 19260950 D01 IV 03/08/1985 03/10/1985 $0 $0 $0 03/26/1985 -  

Investigation Summary

Investigation Nr: 14496160
Event: 12/23/1984
ELECTRIC SHOCK - DIRECT CONTACT WITH REENERGIZED PARTS

TWO EMPLOYEES WERE RELOCATING THE WIRING FOR A 15-KILOVOLT CIRCUIT FROM ONE CABINET TO ANOTHER IN A POWER ROOM FOR A PAPER MILL. POWER TO THE MILL WAS OFF, THE BREAKERS WERE REMOVED, AND THE TERMINALS HAD BEEN TESTED WITH A 'GLOW' STICK AND FOUND TO BE DEENERGIZED. HOWEVER, PROTECTIVE GROUNDS WERE NOT USED. THE EMPLOYEES HAD BEEN WORKING WITH THE CONDUCTORS FOR ABOUT A HALF AN HOUR WHEN THE CONDUCTORS BECAME ENERGIZED FROM AN UNKNOWN SOURCE--POSSIBLY A PORTABLE GENERATOR. ONE EMPLOYEE WAS ELECTROCUTED, AND ANOTHER RECEIVED SEVERE ELECTRIC SHOCK AND BURNS AND WAS HOSPITALIZED.

Keywords: BURN, PROTECTIVE GROUNDING, ELECTRICAL, ELECTROCUTED, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1412436 Fatality Electric Shock Electrical power installers and repairers
2 1412436 Hospitalized injury Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.