Powered by GoogleTranslate

Inspection Detail

Case Status: CLOSED

Inspection: 1404726.015 - Entergy Texas, Inc

Inspection Information - Office: Houston North Area Office

 

Inspection Nr: 1404726.015
Report ID: 0626600
Date Opened: 05/30/2019

Site Address:
Entergy Texas, Inc
54 Still Corner Place
The Woodlands, TX 77380

Mailing Address:
9425 Pine Croft, The Woodlands, TX 77380

Union Status: Union

SIC:

NAICS: 221122/Electric Power Distribution


Inspection Type: Referral

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/30/2019

Emphasis:

Case Closed: 08/16/2019


Related Activity
Type Activity Nr Safety Health
Referral 1460490 Yes
Case Status: CLOSED

Investigation Summary

Investigation Nr: 116695.015
Event: 05/28/2019
Two employees incur burns in arc flash

At 7:35 p.m. on May 28, 2019, Employee #1 and Employee #2 and their coworkers were dispatched to investigate a power outage in a small residential area. During the troubleshooting, a transformer was found in the backyard of a residential home that crew leaders felt was the root cause of the outage and it had to be isolated and replaced. To isolate the transformer, any other transformers that were directly connected to it on the circuit had to be isolated (de-energized) before the removal process began. The isolation process is conducted by pulling the elbow and docking it inside the transformer. The crew isolated the first transformer without issue. The crew went to the next transformer where they found that all the grounds had been burned. The crew could not perform any work on it until the grounds were fixed. Three employees stayed with this transformer and Employee #1 proceeded to the next transformer. After Employee #1 conducted a visual inspection, he found that the area where he was to isolate the elbow was small and he needed a 4-foot shotgun stick. Employee #2 brought him the stick. As Employee #1 removed the elbow, it exploded (arc flashed) blowing employee #2 back against the fence directly behind him and knocking him unconscious. Both employees were taken to the hospital with burns; however, Employee #2 was admitted due to third degree burns while Employee #1 suffered second degree burns and was treated and released.

Keywords: Burn, Electric Arc, Electrical Work, Transformer

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1404726.015 28 M Hospitalized injury Electrical Power-Line
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.