Powered by GoogleTranslate

Inspection Detail

Inspection: 1384619 - Universal Electric Construction Company

Inspection Information - Office: Baton Rouge Area Office

 

Inspection Nr: 1384619
Report ID: 0625700
Date Opened: 05/21/1984

Site Address:
Universal Electric Construction Company
Hwy 61n
Reserve, LA 70084

Mailing Address:
P O Box 37329, Houston, TX 77237

Union Status: NonUnion

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 06/06/1984

Emphasis:

Case Closed: 09/28/1984


Related Activity
Type Activity Nr Safety Health
Accident 360550578
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $560 $0 $0 $0 $0 $560
Current Penalty $280 $0 $0 $0 $0 $280
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260950 C02 I 06/18/1984 06/21/1984 $280 $560 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 14519052
Event: 05/16/1984
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU BOOM

A power line worker was working from an aerial lift, attaching a ground wire to a newly positioned utility pole. The boom of the aerial lift was above a 7620-volt overhead power line. The employee was using an all-metal pneumatic tool with a standard 6.4-millimeter service-station air hose. He was not wearing rubber insulating gloves. The insulated boom had a 140-millimeter by 406-millimeter metal supporting plate underneath. The boom contacted the power line. The air hose, which had not been tested electrically, was corroded with grease and grit and was not capable of withstanding the voltage imposed on it. Consequently, the power line worker was electrocuted.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, AIR HOSE, ELEC UTILITY WORK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1384619 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.