Powered by GoogleTranslate

Inspection Detail

Inspection: 1365790 - Southwestern Public Service Co

Inspection Information - Office: Lubbock Area Office

 

Inspection Nr: 1365790
Report ID: 0627400
Date Opened: 09/11/1984

Site Address:
Southwestern Public Service Co
S Georgia & Fm 1151
Amarillo, TX 79170

Mailing Address:
Po Box 1261, Amarillo, TX 79170

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/12/1984

Emphasis:

Case Closed: 12/05/1984


Related Activity
Type Activity Nr Safety Health
Accident 360552194
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1 2
Current Violations 1 1 2
Initial Penalty $360 $0 $0 $0 $0 $360
Current Penalty $360 $0 $0 $0 $0 $360
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260955 C03 10/22/1984 10/25/1984 $360 $360 $0 -  
2. 02001 Other 19260955 D02 10/22/1984 10/25/1984 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14413363
Event: 09/10/1984
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU NEW LINE

FOUR EMPLOYEES, TWO OF THEM SUPERVISORS, WERE INSTALLING OVERHEAD POWER LINES OVER EXISTING 7620-VOLT OVERHEAD LINES. RUBBER INSULATING LINE HOSE AND INSULATING COVERS HAD BEEN INSTALLED ON THE EXISTING LINES. TWO PHASES HAD BEEN TIED TO PULLING ROPES, AND ONE EMPLOYEE WAS TIEING THE THIRD PHASE TO A ROPE. ONE OF THE SUPERVISORS STATED THAT HE WOULD GET HIS RUBBER GLOVES SO THAT THEY COULD PULL THE LINES ONE AT A TIME. HE TURNED TO GO ABOUT 70 FEET FOR HIS GLOVES, BUT A SECOND EMPLOYEE STARTED PULLING ONE OF THE LINES. AS THE TIE-BACK KNOT CAME TO THE LINE HOSE, IT STUCK AT THE SEAM AND CONTACTED THE CONDUCTOR. THIS ENERGIZED THE CONDUCTOR ON THE GROUND THAT THE FIRST EMPLOYEE WAS HOLDING. HE WAS ELECTROCUTED.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, ELECTROCUTED, E PTD, ELEC UTILITY WORK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1365790 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close