Inspection: 127368223 - Baltimore Gas And Electric Company

Inspection Information - Office: Department Of Labor, Licensing, And Regulation Division Of Labor And Industry Maryland Occupational Safety And Health

 

Inspection Nr: 127368223
Report ID: 0352420
Date Opened: 04/29/1996

Site Address:
Baltimore Gas And Electric Company
4219 Buckskin Lake Drive
Glenelg, MD 21737

Mailing Address:
100 Constellation Way, Baltimore, MD 21202

Union Status: NonUnion

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/24/1996

Emphasis:

Case Closed: 11/26/1996


Related Activity
Type Activity Nr Safety Health
Accident 361542244
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $2,150 $0 $0 $0 $0 $2,150
Current Penalty $1,075 $0 $0 $0 $0 $1,075
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100333 A 08/21/1996 08/26/1996 $1,075 $2,150 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 200960060
Event: 04/26/1996
Electric Shock - Direct Contact with Energized Parts

Two power line workers were assigned to work on a new single-phase, pad-mounted transformer. The employees arrived at the jobsite at 10:00 AM. While they were removing the #1 and #2 elbows, the probes broke off the elbows. They tested both legs at the locations indicated by the feeder print and found the circuit to be deenergized at those locations. However, a line to the transformer was energized from a circuit not shown on the feeder print. The transformer elbow remained energized, and it is believed that the tester being used did not make contact inside the elbow with the conductor lug. Believing from these tests that the line was deenergized, one of the power line workers removed his rubber insulating gloves and received a severe electric shock when he contacted the 7620-volt line. He was hospitalized for his injury.

Keywords: PROTECTIVE GROUNDING, ELECTRICAL, POWER LINE WORKER, EQUIPMENT FAILURE, LOCKOUT, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK, TRANSFORMER

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 127368223 Hospitalized injury Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.