Inspection Detail
Inspection: 127339042 - Robert M Long
Inspection Information - Office: Tennessee Osha Knoxville Office - Safety
Site Address:
Robert M Long
350 Jd Yarnell Industrial Pkwy
Clinton, TN 37716
Mailing Address:
1182 Mchaffey Road, Knoxville, TN 37931
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 07/13/1999
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 08/04/1999
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 361011471 |
Investigation Summary
A crew was installing a jumper in a substation at a plant manufacturing electronic components. The crew had deenergized the circuit but had not drained a capacitor, which had a charge of 11 kilovolts. One of the employees on the crew opened a cabinet and contacted the capacitor. He was electrocuted. The employees had a briefing in the morning, and the cabinet had a warning label.
Keywords: E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, CAPACITOR, ELECTRICAL WORK, LOCKOUT, ELECTRICAL CABINET
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 127339042 | Fatality | Electric Shock | Electricians |