Inspection Detail
Inspection: 127031722 - Cooper Electric
Inspection Information - Office: Miosha Construction Safety & Health Division
Site Address:
Cooper Electric
5425 W Jefferson
Detroit, MI 48209
Mailing Address:
425 E Huron Ave, Vassar, MI 48768
Union Status: NonUnion
SIC:1629
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 05/23/2001
Planning Guide: Safety-Construction
Emphasis: S:Construction
Case Closed: 07/11/2002
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 3 | 3 | 6 | |||
| Current Violations | 3 | 3 | 6 | |||
| Initial Penalty | $2,100 | $0 | $0 | $100 | $0 | $2,200 |
| Current Penalty | $1,050 | $0 | $0 | $100 | $0 | $1,150 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 4084162602 | 06/06/2001 | 06/11/2001 | $500 | $1,000 | $0 | I - Informal Settlement | ||
| 2. | 01002 | Serious | 4084164407 | 06/06/2001 | 06/11/2001 | $200 | $400 | $0 | I - Informal Settlement | ||
| 3. | 01003 | Serious | 4084172511 | 06/06/2001 | 06/11/2001 | $350 | $700 | $0 | I - Informal Settlement | ||
| 4. | 02001 | Other | 4084011401 | 06/06/2001 | 06/11/2001 | $0 | $0 | $0 | - | ||
| 5. | 02002 | Other | 4084184208 | 06/06/2001 | 06/11/2001 | $0 | $0 | $0 | - | ||
| 6. | 03001 | Other | 4082234901 | 10/22/2001 | 10/25/2001 | $100 | $100 | $0 | - |
Investigation Summary
An employee was removing an electric cable. The cable passed through several rooms on its way to an electrical vault. The stone 114 cable to be removed was the fourth cable in the east cable vault room, where the initial cut was performed. It was also the fourth cable in the test portal room, where second cut was performed. However, it was the third cable in west cable vault room. Consequently, the employee misidentified the cable in this room and did not test the cable to determine whether it was energized. The employee cut into a 24-kilovolt Russell 78 cable with a reciprocating saw and created an electrical fault. The ensuing electric arc burned the employee. He was hospitalized for his injuries.
Keywords: BURN, ELECTRIC ARC, ELECTRICAL, ELECTRIC CABLE, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, E C, ELECTRICAL FAULT, UNTRAINED
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 127031722 | Hospitalized injury | Electric Shock | Construction laborers |