Powered by GoogleTranslate

Inspection Detail

Inspection: 126171123 - La County Public Works - Water Treatment Plant

Inspection Information - Office: Van Nuys District Office

 

Inspection Nr: 126171123
Report ID: 0950643
Date Opened: 12/22/1999

Site Address:
La County Public Works - Water Treatment Plant
427 Encinal Canyon Rd.
Malibu, CA 90265

Mailing Address:
1102 N. Eastern Avenue - A&I, Los Angeles, CA 90063

Union Status: Union

SIC:4952

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: LocalGovt

Safety/Health: Health

Close Conference: 05/10/2000

Emphasis:

Case Closed: 06/20/2000


Related Activity
Type Activity Nr Safety Health
Accident 362500035
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $0 $0 $0 $0 $0 $0
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 3203 A07 C 05/19/2000 06/08/2000 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 201112182
Event: 12/09/1999
Employee injured when exposed to chlorine gas

Employee #1, a water treatment worker, was exposed to chlorine gas, which is used to treat the water, when he opened one gas cylinder but did not close the valve on the yoke to prevent the gas from coming out of the disconnected line. Employee #1 was working by himself at a remote location in a small shed-like cabin. Employee #1 works in this facility for three days for about five hours per day. The facility takes sewage water from Camp Miller, a County juvenile detention center and purifies it. Employee #1 was in the process of changing a chlorine gas cylinder. There are two tanks mounted on a weight scale. Employee #1 knows what a full tank weighs and what an empty tank weighs. One of the tanks was almost empty by weight, so Employee #1 shut off the valve of the nearly empty cylinder and opened the valve of the full tank. Each tank has a very small 0.25-inch diameter pvc gas line that goes into a small manifold where both lines meet. There is no bypass valve on the manifold to prevent backflow. Employee #1 then started unscrewing a spring tension valve that holds the yoke to the gas cylinder. The yoke has two spring tension valves; the other side has a valve that would shut an orifice that would prevent the backflow of gas once the yoke is completely disconnected from the gas cylinder. Employee #1 did not screw in the valve which would close the orifice. There were no immediate supervisors around at the time of the accident. The injuries sustained were minimal, a slight irritation of the throat. The factor that caused the accident was a lack of proper training in the changeover process. While Employee #1 was trained in the changeover, no one told him to shut of the valve to the orifice before removing the yoke. Employee #1 was taken to Los Robles Hospital in Thousand Oaks, California, where he was hospitalized and kept overnight for observation.

Keywords: ASPHYXIATED, CYLINDER, GAS, CHLORINE, VALVE, ACCIDENTAL DISCHARGE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 126171123 Hospitalized injury Asphyxia Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close