Inspection: 126157874 - La City Water & Power
Inspection Information - Office: Los Angeles District Office
Site Address:
La City Water & Power
10945 1/2 Le Conte Ave.
Los Angeles, CA 90095
Mailing Address:
111 N. Hope St., Ste. 1532, Los Angeles, CA 90012
Union Status: Union
SIC:4911
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: LocalGovt
Safety/Health: Safety
Close Conference: 06/21/2002
Emphasis:
Case Closed: 11/12/2002
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 362584690 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 1 | ||||
Current Violations | 1 | 1 | ||||
Initial Penalty | $18,000 | $0 | $0 | $0 | $0 | $18,000 |
Current Penalty | $18,000 | $0 | $0 | $0 | $0 | $18,000 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 23200002 A05 | 11/12/2002 | 11/15/2002 | $18,000 | $18,000 | $0 | - |
Investigation Summary
A five-person power line crew was assigned to install a three-phase service from a pad-mounted transformer to a new meter cabinet. The 480/277-volt circuit remained energized while the employees were working, despite the limited working space for the bolts they were to install. They covered energized parts with a rubber insulating blanket. However, they left the terminal on which they were working and the back plate of the terminals uncovered. The employees connected the first terminal without incident. On the second terminal, the supervisor on the crew dropped a bolt he was inserting. The bolt caused an electrical fault between the terminal and the back plate. The ensuing electric arc burned the supervisor on the face. He was hospitalized for his injuries.
Keywords: BURN, ELECTRIC ARC, ELECTRICAL, POWER LINE WORKER, ELECTRIC METER, E PTD, ELEC UTILITY WORK, ELECTRICAL FAULT, FACE, TRANSFORMER
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 126157874 | Hospitalized injury | Burn/Scald(Heat) | Supervisors; electricians & power transm. install. |