Powered by GoogleTranslate

Inspection Detail

Inspection: 126155753 - Building & Computer Electric Inc

Inspection Information - Office: Los Angeles District Office

 

Inspection Nr: 126155753
Report ID: 0950641
Date Opened: 10/22/2002

Site Address:
Building & Computer Electric Inc
1100 S. Glendon Ave.
Los Angeles, CA 90024

Mailing Address:
1150 S. Olive St., Ste. 112, Los Angeles, CA 90012

Union Status: NonUnion

SIC:1731

NAICS: 238210/Electrical Contractors


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Health

Close Conference: 03/27/2003

Emphasis: S:Construction (Cship)

Case Closed: 04/02/2003


Related Activity
Type Activity Nr Safety Health
Accident 362588923
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $0 $0 $0 $450 $0 $450
Current Penalty $0 $0 $0 $450 $0 $450
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 23200002 A01 04/01/2003 04/01/2003 $450 $450 $0 -  

Investigation Summary

Investigation Nr: 201164266
Event: 10/17/2002
Employee injured in fall after electric shock

At approximately 8:20 a.m. on October 17, 2002, Employee #1 was splicing new wires into a junction box in the ceiling of a building in Los Angeles, CA. He was standing on an approximately 6 ft ladder and opening the neutral wires and spreading them out. He was holding onto a ceiling wire with his left hand and putting down his screwdriver and wire strippers with his right hand when the wire touched his right arm. He felt an electric current go through his right hand from the 480-volt eneregized wire. Employee #1 screamed for help and tried to kick the ladder out from under himself, but he was wedged in the ceiling. A coworker rushed over and grabbed him by the legs to pull him out, but the action further wedged him in because of the presence of metal studs. Another coworker immediately grabbed a ladder and positioned it on Employee #1's left hip with the intent of turning him around. When that didn't work, the coworker struck him two or three times with the ladder. Employee #1 fell approximately 8 ft to the floor, landing with his left shoulder on the ladder that was laying there. He suffered third-degree burns on his left hand and an impacted left sholder. Paramedics were called and he was transported to the UCLA Hospital and then transferred to the Grossman Burn Center, where he was hospitalized for one week. Employee #1 stated that he had used a Tic Tracer to test the circuits in the ceiling to determine if they were energized. Upon evaluation, the Tic Tracer was found to give false readings.

Keywords: BURN, WORK RULES, LADDER, STRUCK AGAINST, CONSTRUCTION, TEST EQUIPMENT, CAUGHT BETWEEN, ELEC CIRC PART--MISC, FALL, HAND

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 126155753 Hospitalized injury Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.