Powered by GoogleTranslate

Inspection Detail

Inspection: 126133859 - Driftwood Dairy

Inspection Information - Office: Monrovia District Office

 

Inspection Nr: 126133859
Report ID: 0950644
Date Opened: 03/31/1998

Site Address:
Driftwood Dairy
10724 Lower Azusa Rd.
El Monte, CA 91731

Mailing Address:
, , 00000

Union Status: Union

SIC:5143

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/19/1998

Emphasis:

Case Closed: 04/08/2000


Related Activity
Type Activity Nr Safety Health
Accident 362266678
Accident 362533879
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $5,000 $0 $0 $0 $0 $5,000
Current Penalty $0 $0 $0 $300 $0 $300
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 23950051 A01 06/19/1998 07/01/1998 $300 $5,000 $0 07/20/1998 J - ALJ Decision  

Investigation Summary

Investigation Nr: 201791241
Event: 03/23/1998
electric shock - ground fault in electric pump

An employee of a dairy firm was preparing to mix concentrated orange juice with water. All the mixing pumps were turned off. When he turned on the timer for the orange juice pump and refrigeration unit (Sterling Electric, Serial No. 88-4191-2, Frame No. 215-T-73- 25, 240 volts, 7.5 kilowatt, 26.4 amps. three-phase motor), he received an electric shock and lost consciousness. After regaining consciousness, the employee said that the last things that he remembered were that he had his right hand on the body of the pump, and he pushed the start button with his right thumb while he was holding a steel pipe with his left hand. An investigation determined that the equipment grounding conductor for the unit was not connected on the grounding plate at the control panel. The injured employee was hospitalized.

Keywords: E GI V, ELECTRICAL, INADEQUATE MAINT, GROUND FAULT, EQUIPMENT GROUNDING, ELECTRIC SHOCK, ELEC EQUIPMENT--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 126133859 Hospitalized injury Electric Shock Administrative support occupations, n.e.c.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.