Inspection Detail
Inspection: 126110709 - Pg & E
Inspection Information - Office: Labor Enforcement Task Force (Letf) Unit - South
Site Address:
Pg & E
San Barnardo Creek Rd.
San Luis Obispo, CA 93401
Mailing Address:
77 Beale St, San Francisco, CA 94105
Union Status: Union
SIC:4911
NAICS: 221111/Hydroelectric Power Generation
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 03/30/2004
Emphasis:
Case Closed: 06/29/2004
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 362497026 |
Investigation Summary
A power line worker was replacing dampers on a metal tower supporting a two-circuit, 115-kilovolt overhead power line. The line on which he was replacing the dampers was deenergized, but the parallel circuit was not. The crew had changed dampers on several towers. This was the first tower for the power line worker to change dampers on this day. Without waiting for the grounding equipment to be raised, the employee started to work on the dampers. He was electrocuted when he contacted one of the power line conductors. The parallel energized line had induced voltage on the deenergized line. The employee had performed this task many times before and was trained for the work.
Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, PROTECTIVE GROUNDING, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, INDUCED CURRENT, ELEC UTILITY WORK
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 126110709 | Fatality | Electric Shock | Electrical power installers and repairers |