Inspection Detail
Inspection: 126105311 - Angeles Electric Company
Inspection Information - Office: Los Angeles District Office
Site Address:
Angeles Electric Company
2401 Colorado Ave., 2nd Fl.
Santa Monica, CA 90404
Mailing Address:
9325 Atlantic Ave., South Gate, CA 90280
Union Status: Union
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 05/11/2001
Planning Guide: Safety-Construction
Emphasis: S:Construction (Cship)
Case Closed: 01/15/2004
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 362570913 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 2 | 1 | 3 | |||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $9,900 | $0 | $0 | $275 | $0 | $10,175 |
| Current Penalty | $550 | $0 | $0 | $0 | $0 | $550 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 1509 C | 05/11/2001 | 05/16/2001 | $0 | $275 | $0 | 07/06/2001 | F - Formal Settlement | Citation has been deleted. |
| 2. | 02001 | Serious | 23200003 | 05/11/2001 | 05/16/2001 | $550 | $4,950 | $0 | 07/06/2001 | F - Formal Settlement | |
| 3. | 03001 | Serious | 23200004 A04 | 05/11/2001 | 05/16/2001 | $0 | $4,950 | $0 | 07/06/2001 | F - Formal Settlement | Citation has been deleted. |
Investigation Summary
An electrician was assigned to remove an overhead lighting fixture. The circuit supplying the fixture was deenergized. The electrician was standing on a 1.8-meter-tall ladder disconnecting the fixture from the circuit. When he touched the wiring, he felt an electric shock. He then pulled on a conductor with a bare end and received an electric shock from the 277-volt conductor for about 10 seconds. His left shoulder was touching a water pipe. He was knocked unconscious and fell from the ladder. He regained consciousness at a hospital, where he was treated for two wounds on his right index finger and released the same day. Investigation showed that neither the electrician nor his supervisor knew that there was an energized emergency line near the fixture. The supervisor had been certain that the lighting fixture was deenergized.
Keywords: E GI IV, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR, ELECTRIC SHOCK, FALL
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 126105311 | Non Hospitalized injury | Electric Shock | Electricians |