Powered by GoogleTranslate

Inspection Detail

Inspection: 126069707 - Don Tobias Dba Tec Tobias Builders

Inspection Information - Office: Long Beach District Office

 

Inspection Nr: 126069707
Report ID: 0950635
Date Opened: 07/25/2002

Site Address:
Don Tobias Dba Tec Tobias Builders
19600 Jacob Ave
Cerritos, CA 90703

Mailing Address:
2147 West Crestwood, Anaheim, CA 92804

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/02/2002

Emphasis:

Case Closed: 09/13/2010


Related Activity
Type Activity Nr Safety Health
Accident 362433971
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 4 5
Current Violations 2 2
Initial Penalty $14,400 $0 $0 $1,485 $0 $15,885
Current Penalty $0 $0 $0 $785 $0 $785
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 342 A 01/15/2003 12/10/2002 $0 $350 $0 06/06/2003 J - ALJ Decision Citation has been deleted.
2. 01002 Other 14300007 B03 11/12/2002 12/10/2002 $350 $350 $0 06/06/2003 W - Empr Withdrew  
3. 01003 Other 3203 B02 01/15/2003 12/10/2002 $0 $350 $0 06/06/2003 J - ALJ Decision Citation has been deleted.
4. 01004 Other 1509 A 11/12/2002 12/10/2002 $435 $435 $0 06/06/2003 W - Empr Withdrew  
5. 02001 Serious 23200004 A02 01/15/2003 11/15/2002 $0 $14,400 $0 06/06/2003 J - ALJ Decision Citation has been deleted.

Investigation Summary

Investigation Nr: 201034303
Event: 07/16/2002
Employee burned by electrical flash from switchgear

On July 16, 2002, Employee #1, an electrician with Tobias Builders, was helping to replace old equipment in the main electrical room of the Nixon Elementary School in Cerritos, CA. The job was part of overall renovation and remodelling work underway during the summer vacation period. On the day before the accident, Employee #1 had discussed the first part of the job with his supervisor, which was to remove the electrical equipment from the east wall of the approximately 15 ft by 20 ft main electrical room. Shortly before 9:00 a.m., Employee #1 was in front of the 480-volt, 800-amp Zinsco switchgear, catalog #FDP 368T, on the east wall of the room. It had the meter section on the left-hand side (with the main disconnect), along with Southern California Edison's (SCE) feed. The right-hand load section had the following: (1) five disconnect switches (AC1 through AC5 for the air conditioning system and arranged in a vertical plane); (2) another disconnect for a transformer; and (3) the last disconnect switch (HA/HB), which was connected to other panels inside the building. Employee #1 turned each disconnect lever to switch off AC1 through AC5 and HA/HB. The transformer disconnect was not switched off, apparently to have power for other purposes while construction operations were underway. Immediately after turning off the switches, he started pulling the disconnected wire/cable ends of HA/HB from the conduit that was protruding at floor level. There was an instantaneous explosion/flash in front of Employee #1 from the right-hand side panel, AC3. He turned his face and stepped back, sustaining burns to his right hand and to the lower left side of his face. He was initially taken to La Palma Inter Community Hospital and was later transferred to Grossman Hospital at Sherman Oaks, where he was treated for three days. The cause of the accidnt was Employee #1's failure to disconnect/lockout the main SCE feed line on the meter section of the panel.

Keywords: BURN, MAINTENANCE, WORK RULES, CONSTRUCTION, ELECTRICAL WORK, LOCKOUT, ELEC CIRC PART--MISC, ELECTRICAL FAULT, SWITCHGEAR, FACE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 126069707 Hospitalized injury Burn/Scald(Heat) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close