Inspection Detail
Inspection: 125998690 - San Diego Gas & Electric
Inspection Information - Office: San Diego District Office
Site Address:
San Diego Gas & Electric
1/4 Mi. East Of Live Oak Springs/ 1/2 Mi North Of
Hwy 94 County Of San Diego, CA 92036
Mailing Address:
P.O Box 1831, San Diego, CA 92112
Union Status: Union
SIC:4939
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 06/30/1997
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 10/20/1998
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 362254112 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | ||||||
| Initial Penalty | $5,000 | $0 | $0 | $0 | $0 | $5,000 |
| Current Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 2717 | 07/03/1997 | 07/18/1997 | $0 | $5,000 | $0 | 08/04/1997 | J - ALJ Decision | Citation has been deleted. |
Investigation Summary
A four-person power line crew was reconfiguring a 69-kilovolt overhead power line supported by a wood utility pole. The crew was replacing the crossarm and suspension insulators with post insulators. Two of the power line workers climbed the pole to perform the work. As part of the job, they had to remove the existing, deteriorated crossarm. While one employee was loosening the bolt on the 3-meter-long crossarm, the other employee tried to pull the cross arm out. Because the bolt had not been completely removed, the crossarm pivoted and contacted a suspension clamp. This caused an electrical fault. The employee closest to the ensuing electric arc received an electric shock and was burned on his back, arms, legs, and feet. He also sustained burns to some internal organs. He was hospitalized for his injuries.
Keywords: BURN, CLOTHING, ELECTRIC ARC, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK, ELECTRICAL FAULT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 125998690 | Hospitalized injury | Electric Shock | Electrical power installers and repairers |
Translate