Inspection Detail
Inspection: 125908822 - Hampton Tedder Electric
Inspection Information - Office: Santa Ana District Office
Site Address:
Hampton Tedder Electric
Corner Of Grand & 4th
Santa Ana, CA 92705
Mailing Address:
4571 State St, Montclair, CA 91763
Union Status: Union
SIC:4911
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 01/15/1998
Planning Guide: Safety-Manufacturing
Emphasis:
Case Closed: 06/30/1998
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 362229437 | ||
| Accident | 362229452 |
Investigation Summary
A power line crew of four employees was ringing out the phases of a 12-kilovolt power line as part of a project to convert an overhead power line to underground. The task involved using headphones after disconnecting a cable at the both ends. One employee working on the ground disconnected an elbow and connected his headphone lead to the elbow end of the cable. The 12-kilovolt cable was still energized from the overhead end. The headphone failed, creating an electrical fault. The ensuing electric arc caused second- and third-degree burns to the employee's face, chest, and arms. He was hospitalized for his injuries.
Keywords: BURN, CLOTHING, ELECTRIC ARC, ELECTRICAL, POWER LINE WORKER, LOCKOUT, E PTD, ELEC UTILITY WORK, ELECTRIC CONDUCTOR, ELECTRICAL FAULT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 125908822 | Hospitalized injury | Other | Electrical and electronic technicians |
Translate