Powered by GoogleTranslate

Inspection Detail

Inspection: 125908061 - Champ Steel

Inspection Information - Office: Santa Ana District Office

 

Inspection Nr: 125908061
Report ID: 0950631
Date Opened: 07/09/1997

Site Address:
Champ Steel
5301 Bolsa Ave
Huntington Beach, CA 92647

Mailing Address:
633 E Young St, Santa Ana, CA 92705

Union Status: Union

SIC:3721

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/22/1997

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 05/09/2003


Related Activity
Type Activity Nr Safety Health
Accident 362216384
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 1 3
Current Violations 1 2 3
Initial Penalty $6,500 $0 $0 $600 $0 $7,100
Current Penalty $0 $0 $0 $750 $0 $750
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 2944 H01 B 09/26/1997 10/19/1997 $600 $600 $0 -  
2. 02001 Other 2811 09/26/1997 10/19/1997 $150 $5,000 $0 F - Formal Settlement  
3. 03001 Serious 2940 B 09/26/1997 10/19/1997 $0 $1,500 $0 D - Govt Dismissed  

Investigation Summary

Investigation Nr: 201140373
Event: 04/26/1997
BURN - VOLTAGE TESTER FAILED

An electrician was working in a substation. He was performing preventive maintenance, cleaning the low-voltage (480-volt) side of a transformer. The electrician tried to test the incoming high-voltage (12-kilovolt) conductors with a tester rated for 600 volts maximum. The tester failed, and the ensuing electric arc burned the employee. He sustained second- and third-degree burns to both his hands and to his face. He was hospitalized for his injuries.

Keywords: BURN, ELECTRIC ARC, ELECTRICAL, ELECTRICIAN, EQUIPMENT FAILURE, TEST EQUIPMENT, E PTD, ELEC UTILITY WORK, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 125908061 Hospitalized injury Burn/Scald(Heat) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.