Inspection Detail
Inspection: 125879023 - Trs Electric
Inspection Information - Office: San Diego District Office
Site Address:
Trs Electric
19086 Via Ambiente
San Diego, CA 92024
Mailing Address:
1885 S. Vineyard Ave. Ste. 3, Ontario, CA 91761
Union Status: NonUnion
SIC:1731
NAICS: 238210/Electrical Contractors
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 01/22/2007
Emphasis:
Case Closed: 03/18/2009
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 101062495 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 3 | 4 | 7 | |||
| Current Violations | 1 | 3 | 4 | |||
| Initial Penalty | $19,350 | $0 | $0 | $680 | $0 | $20,030 |
| Current Penalty | $14,400 | $0 | $0 | $200 | $0 | $14,600 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 3203 A04 | 01/23/2007 | 03/12/2007 | $100 | $135 | $0 | 01/29/2007 | F - Formal Settlement | |
| 2. | 01002 | Other | 3203 B01 | 01/23/2007 | 03/12/2007 | $0 | $135 | $0 | 01/29/2007 | F - Formal Settlement | |
| 3. | 01003 | Other | 3314 G01 B | 01/23/2007 | 03/12/2007 | $0 | $275 | $0 | 01/29/2007 | F - Formal Settlement | Citation has been deleted. |
| 4. | 01004 | Other | 3314 J01 | 01/23/2007 | 03/12/2007 | $100 | $135 | $0 | 01/29/2007 | F - Formal Settlement | |
| 5. | 02001 | Serious | 23200002 A04 | 01/23/2007 | 02/26/2007 | $0 | $2,475 | $0 | 01/29/2007 | F - Formal Settlement | Citation has been deleted. |
| 6. | 03001 | Serious | 23200002 A06 | 01/23/2007 | 02/06/2007 | $0 | $2,475 | $0 | 01/29/2007 | F - Formal Settlement | Citation has been deleted. |
| 7. | 04001 | Serious | 23200003 | 01/23/2007 | 02/06/2007 | $14,400 | $14,400 | $0 | 01/29/2007 | F - Formal Settlement |
Investigation Summary
At approximately 1:00 p.m. on August 31, 2006, Employee #1 was conducting electrical preventive maintenance and testing on Switchboard RM-3 at the San Diego County Water Authority's Olivenhain Pumping Statio. RM-3 was a three-phase, four wire metering station of 277/480 volts and 1,600 apms. He was using a ductor testing device on the switchboard while cleaning the insulators around the busbar. Employee #1 had moved the clamp on the ductor tester equipment from the Phase A bus to the Phase B bus when the breaker flashed, causing an explosion. He suffered second- and third-degree burns to his left forearm and palm, as well as lesser burns to his face and ear. Employee #1's supervisor was walking to the pumping station when the explosion occurred, and he called 911. Employee #1 was transported by ambulanced from the dam to meet a medical helicopter. He was then airlifted to the UC-San Diego Burn Center. As of September 5, 2006, Employee #1 remained hospitalized. He expected to be released soon, but did not know when he would be able to return to work.
Keywords: BURN, MAINTENANCE, ELECTRICAL, FOREARM, BUSBAR, CONSTRUCTION, ELEC CIRC PART--MISC, ELECTRICAL FAULT, FACE
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 125879023 | Fatality | Electric Shock | Electricians |