Inspection Detail
Inspection: 125867598 - Martinez Refining Company
Inspection Information - Office: American Canyon District Office
Site Address:
Martinez Refining Company
1800 Marina Vista
Martinez, CA 94553
Mailing Address:
Po Box 711, Martinez, CA 94553
Union Status: Union
SIC:2911
NAICS: 324110/Petroleum Refineries
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 07/20/1998
Emphasis:
Case Closed: 10/01/1998
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 362083602 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 2 | 2 | ||||
Current Violations | 2 | 2 | ||||
Initial Penalty | $0 | $0 | $0 | $525 | $0 | $525 |
Current Penalty | $0 | $0 | $0 | $525 | $0 | $525 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Other | 6778 | 08/04/1998 | 08/04/1998 | $350 | $350 | $0 | - | ||
2. | 01002 | Other | 6846 C | 08/04/1998 | 08/04/1998 | $175 | $175 | $0 | - |
Investigation Summary
Employee #1, a boiler operator, sustained first and second-degree burns when 650 psig steam and 495 degrees Fahrenheit hot water erupted out of an atmospheric vent located 8-to-9 inches above his work location on the deck. Employee #1 was able to remove himself from the upper deck; however, his escape was hampered by the presence of piping and appurtenances. Employee #1 had "cracked" open a 2-inch vent valve which had been leaking. Over a period of time the steam leaking by the valve had condensed in the 4-inch vent line and it combined somewhat violently with the 650 psig steam once the operator opened the vent valve. The resulting discharge from the atmospheric vent was not mitigated by a diverter on the vent or by the presence of a protective canopy above Employee #1's work location at the valve. Employee #1 was hospitalized for three days; however, skin grafts were not necessary. Employee #1 has since returned to full duties.
Keywords: BURN, VENTING, BOILER, STEAM, VALVE, SKIN, ACCIDENTAL DISCHARGE
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 125867598 | Hospitalized injury | Burn/Scald(Heat) | Power plant operators |