Inspection Detail
Inspection: 125861823 - Snp Electric
Inspection Information - Office: Sacramento District Office
Site Address:
Snp Electric
4925 Dewey Dr
Fair Oaks, CA 95628
Mailing Address:
5800 Jameson Ct, Carmichael, CA 95608
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 01/27/2000
Emphasis:
Case Closed: 12/06/2000
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 361498249 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | 2 | |||
| Current Violations | 1 | 1 | 2 | |||
| Initial Penalty | $3,000 | $0 | $0 | $150 | $0 | $3,150 |
| Current Penalty | $3,000 | $0 | $0 | $150 | $0 | $3,150 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 3203 A | 01/27/2000 | 02/25/2000 | $150 | $150 | $0 | - | ||
| 2. | 02001 | Serious | 23200002 A | 01/27/2000 | 02/01/2000 | $3,000 | $3,000 | $0 | 02/07/2000 | W - Empr Withdrew |
Investigation Summary
Two employees of an electrical contractor were running new conduit at a school. However, they were not connecting any wiring. They were running 19-millimeter-diameter conduit between a circuit breaker panelboard and a 480-volt transformer cabinet. One of the employees, an electrician, was installing bushings and clamps inside the transformer cabinet while it was energized. His wristwatch contacted energized parts, and the electrician received an electric shock and was knocked unconscious. (The employee's normal practice had been to deenergize the circuit and remove any jewelry.) His coworker and emergency medical services administered first aid and cardio-pulmonary resuscitation to no avail. The employee died of electrocution.
Keywords: ELEC PROTECT EQUIP, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, TRANSFORMER
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 125861823 | Fatality | Electric Shock | Electricians |