Inspection Detail
Inspection: 125844290 - Comm Air
Inspection Information - Office: American Canyon District Office
Site Address:
Comm Air
2674 Vassar
Merced, CA 95340
Mailing Address:
5499 E. Hedges Avenue, Fresno, CA 93727
Union Status: Union
SIC:1711
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 10/26/2000
Emphasis: S:Construction (Cship)
Case Closed: 10/26/2000
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 362089773 |
Investigation Summary
A heating, ventilation, and air conditioning worker with 32 years of experience was replacing a disconnect for a 480-volt compressor. The employee had deenergized the entire room. Using a flashlight, the employee removed the old disconnect, installed a new one, and connected the supply conductors. He then reenergized the compressors. He believed that the wiring on the load side of the disconnect was deenergized. However, he had not noticed that the replacement disconnect was in the closed position when he removed it from the box. As the employee was tightening the screws on the fuse clips on the disconnect cabinet, the screwdriver contacted the metal enclosure, causing an electrical fault. The ensuing electric arc burned the employee. He sustained first- and second-degree burns to his hands and face.
Keywords: BURN, FUSE, ELECTRIC ARC, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, ELECTRICAL CABINET, ELECTRICAL FAULT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 125844290 | Non Hospitalized injury | Electric Shock | Heating, air conditioning, and refrig. mechanics |