Powered by GoogleTranslate

Inspection Detail

Inspection: 125829721 - Pacific Corp. Dba Pacific Power & Light

Inspection Information - Office: Sacramento District Office

 

Inspection Nr: 125829721
Report ID: 0950621
Date Opened: 03/24/2005

Site Address:
Pacific Corp. Dba Pacific Power & Light
Laird'S Landing
Macdoel, CA 96058

Mailing Address:
1950 Mallard Lane, Klamath Falls, OR 97601

Union Status: Union

SIC:4911

NAICS: 221122/Electric Power Distribution


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 03/24/2005

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 04/23/2007


Related Activity
Type Activity Nr Safety Health
Accident 101172211
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $0 $0 $0 $600 $0 $600
Current Penalty $0 $0 $0 $600 $0 $600
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 2941 H11 08/23/2005 08/26/2005 $600 $600 $0 -  

Investigation Summary

Investigation Nr: 201177425
Event: 03/04/2005
Electric Shock - Direct Contact with Energized Conductor

On March 4, 2005, Employee #1, a journeyman lineman, was working for the electric utility Pacific Power and Light, a division of PacifiCorp. He was placing a fuse in a 12-kV line. He did not place a jumper, or ground line, on both sides of the conductor that he had cut. This omission caused a lack of continuity in the grounding system. On the utility pole above the 12-kV on which he was working was a 69-kV line, which was energized. The 69-kV line induced a voltage in the 12-kV line, and Employee #1 received an electric shock. He was hospitalized.

Keywords: FUSE, OVERHEAD POWER LINE, E GI IV, ELECTRICAL, POTENTIAL GRADIENT, BONDING, INDUCED CURRENT, ELEC UTILITY WORK, ELECTRIC SHOCK, UTILITY POLE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 125829721 Hospitalized injury Electric Shock Misc. electrical & electronic equipment repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close