Inspection Detail
Inspection: 125803346 - Ca Exposition & State Fair
Inspection Information - Office: Sacramento District Office
Site Address:
Ca Exposition & State Fair
1600 Exposition Blvd
Sacramento, CA 95815
Mailing Address:
, , 00000
Union Status: Union
SIC:7999
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: StateGovt
Safety/Health: Safety
Close Conference: 07/27/1999
Emphasis:
Case Closed: 11/30/1999
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 361501091 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 3 | 3 | ||||
Current Violations | 3 | 3 | ||||
Initial Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
Current Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Other | 23400023 | 11/01/1999 | 11/04/1999 | $0 | $0 | $0 | - | ||
2. | 01002 | Other | 23200002 A03 | 11/01/1999 | 11/18/1999 | $0 | $0 | $0 | - | ||
3. | 01003 | Other | 23200002 A04 | 11/01/1999 | 11/18/1999 | $0 | $0 | $0 | - |
Investigation Summary
An electrician went to an electrical room to replace the fuses in some fuse holders. He set the fuses down in the cabinet to put his gloves on. He accidentally touched one of the fuses to a 277-volt conductor and a ground, causing an electrical fault. The ensuing electric arc severely burned the employee on his right arm and face. He was hospitalized for his injuries.
Keywords: BURN, FUSE, ELECTRIC ARC, E GI III, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, ELECTRICAL CABINET, ELECTRICAL FAULT
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 125803346 | Hospitalized injury | Burn/Scald(Heat) | Electricians |