Powered by GoogleTranslate

Inspection Detail

Inspection: 125793505 - Sierra Pacific Industries

Inspection Information - Office: Sacramento District Office

 

Inspection Nr: 125793505
Report ID: 0950621
Date Opened: 05/05/1997

Site Address:
Sierra Pacific Industries
1445 Hwy 65
Lincoln, CA 95648

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:2421

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/01/1997

Emphasis:

Case Closed: 10/30/1997


Related Activity
Type Activity Nr Safety Health
Accident 361503626
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1 2
Current Violations 1 1 2
Initial Penalty $1,060 $0 $0 $425 $0 $1,485
Current Penalty $1,060 $0 $0 $425 $0 $1,485
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 23200002 A03 07/01/1997 07/03/1997 $425 $425 $0 -  
2. 02001 Serious 23200002 A04 07/01/1997 07/11/1997 $1,060 $1,060 $0 -  

Investigation Summary

Investigation Nr: 201170289
Event: 05/03/1997
BURN - ELECTRICAL FAULT IN TEST INSTRUMENT

Three millwrights were building a mill from salvaged equipment. On the day of the accident, they were installing salvaged electric equipment. They were testing several electrical connections in the motor starter cabinet to locate a particular conductor. The lead millwright had been using a wiggy to test the voltages on the 480-volt system. After making several tests, he decided to change to a Fluke meter to obtain readings that were more precise. The Fluke meter had the leads connected to the wrong terminals, the ones for testing current instead of voltage. When he touched the meter leads to the first connection, the meter failed, creating an electrical fault. The ensuing electric arc burned the three millwrights. All three employees were hospitalized for their injuries. Two of them were released the next day; the third millwright was very seriously burned and placed in the burn ward of the hospital.

Keywords: BURN, CLOTHING, E GI V, ELECTRIC ARC, ELECTRICAL, ELECTRICAL TESTING, EQUIPMENT FAILURE, TEST EQUIPMENT, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 125793505 Hospitalized injury Burn/Scald(Heat) Millwrights
2 125793505 Hospitalized injury Burn/Scald(Heat) Millwrights
3 125793505 Non Hospitalized injury Burn/Scald(Heat) Millwrights
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.