Inspection Detail
Inspection: 125741702 - Enxco
Inspection Information - Office: American Canyon District Office
Site Address:
Enxco
7601 Byron Hot Springs Rd.
Byron, CA 94514
Mailing Address:
Po Box 581043, North Palm Springs, CA 92258
Union Status: NonUnion
SIC:4911
NAICS: 221119/Other Electric Power Generation
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 02/13/2003
Emphasis:
Case Closed: 05/24/2005
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 361733900 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 2 | 2 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $0 | $0 | $0 | $600 | $0 | $600 |
| Current Penalty | $0 | $0 | $0 | $300 | $0 | $300 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 25000010 A | 03/11/2003 | 04/13/2003 | $300 | $300 | $0 | - | ||
| 2. | 01002 | Other | 3382 A | 03/11/2003 | 12/11/2002 | $0 | $300 | $0 | 05/16/2003 | F - Formal Settlement | Citation has been deleted. |
Investigation Summary
An employee was working beneath a 480-volt cabinet inside a wind turbine tower. He repeatedly pushed against three cables to access a bracket. The cables pulled loose and created an electrical fault. The ensuing electric arc burned the employee and started a fire. The employee was initially treated at a medical facility, released, and directed to go to the company doctor the following day. After the injured employee visited the company doctor, he was transported by ambulance to a different medical facility, where he was hospitalized 6 days for second- and third-degree burns to his neck, face, and hands and to an ear.
Keywords: BURN, ELECTRIC ARC, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, E PTD, ELEC UTILITY WORK, ELECTRICAL CABINET, ELECTRICAL FAULT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 125741702 | Hospitalized injury | Burn/Scald(Heat) | Technicians, n.e.c. |