Powered by GoogleTranslate

Inspection Detail

Inspection: 125629402 - International Line Builders

Inspection Information - Office: Oakland District Office

 

Inspection Nr: 125629402
Report ID: 0950614
Date Opened: 11/27/2000

Site Address:
International Line Builders
19131 Crest Avenue
Castro Valley, CA 94546

Mailing Address:
P O Box 23729, Portland, OR 97281

Union Status: Union

SIC:1623

NAICS: 0 


Inspection Type: Unprog Rel

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/25/2001

Emphasis:

Case Closed: 06/25/2002


Related Activity
Type Activity Nr Safety Health
Accident 361493083
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations
Initial Penalty $35,800 $0 $0 $0 $0 $35,800
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 29400002 A 05/25/2001 05/30/2001 $0 $25,000 $0 06/06/2001 J - ALJ Decision Citation has been deleted.
2. 02001 Serious 4001 05/25/2001 06/04/2001 $0 $5,400 $0 06/06/2001 J - ALJ Decision Citation has been deleted.
3. 03001 Serious 3638 E 05/25/2001 06/04/2001 $0 $5,400 $0 06/06/2001 J - ALJ Decision Citation has been deleted.

Investigation Summary

Investigation Nr: 201502382
Event: 11/27/2000
Electric Shock - Direct Contact with Overhead Line

A power line worker was working from an aerial lift. He was working on a deenergized transformer. The operating controls for the aerial lift became entangled in a loop of secondary lead conductor, which caused the bucket on the aerial lift to ascend. This crushed and buckled the fiberglass bucket against the transformer. When the bucket was moved away from the transformer, it sprang back into shape, catapulting the employee into a 6950-volt overhead power line. The employee was electrocuted.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, AERIAL LIFT CONTROLS, ENTANGLED, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 125629402 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close