Powered by GoogleTranslate

Inspection Detail

Inspection: 125530477 - Degryse Electric

Inspection Information - Office: American Canyon District Office

 

Inspection Nr: 125530477
Report ID: 0950615
Date Opened: 01/06/2005

Site Address:
Degryse Electric
530 Francisco Blvd W
San Rafael, CA 94901

Mailing Address:
4412 Technology Drive, Fremont, CA 94538

Union Status: NonUnion

SIC:1629

NAICS: 236210/Industrial Building Construction


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 02/10/2005

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 04/24/2006


Related Activity
Type Activity Nr Safety Health
Accident 361601545
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $0 $0 $0 $110 $0 $110
Current Penalty $0 $0 $0 $110 $0 $110
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 1637 A 02/14/2005 02/17/2005 $110 $110 $0 -  

Investigation Summary

Investigation Nr: 170842900
Event: 01/05/2005
Employee burned by electric arc flash

At 6:15 a.m. on January 15, 2005, Employee #1, a journeyman electrician, was installing a new power panel during the remodeling of a unit at a strip mall. He was putting in a mechanical lug on a busbar, above the main breaker on the load side. The breaker was turned off, but the incoming busbars below the breaker were energized with 480-volt, three-phase power. Employee #1 was standing on a 13 in. tall by 16 in. diameter empty wooden cable spool to reach the lug location. As he tightened the lug, he dropped the ratchet and socket wrench, which landed between the metal dead front on the panel and a live incoming busbar below the main breaker. This caused a short circuit and arc flash. Employee #1 sustained burns to his stomach, face, and hands. The burns to his hands required hospitalization for skin grafts.

Keywords: BURN, ELECTRIC ARC, ELECTRICAL, CONSTRUCTION, ELEC CIRC PART--MISC, ELECTRICAL CABINET, ELECTRICAL FAULT, HAND TOOL, HAND

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 125530477 Hospitalized injury Burn/Scald(Heat) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close