Inspection: 125493106 - Decker Electric
Inspection Information - Office: San Francisco District Office
Site Address:
Decker Electric
600 Battery Street
San Francisco, CA 94111
Mailing Address:
1282 Folsom St., San Francisco, CA 94103
Union Status: Union
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 05/23/2000
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 01/26/2001
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 361568876 | ||
| Accident | 361571201 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 2 | 3 | |||
| Current Violations | 1 | 2 | 3 | |||
| Initial Penalty | $18,000 | $0 | $0 | $450 | $0 | $18,450 |
| Current Penalty | $2,700 | $0 | $0 | $450 | $0 | $3,150 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 342 A | 07/18/2000 | 07/21/2000 | $300 | $300 | $0 | F - Formal Settlement | ||
| 2. | 01002 | Other | 1509 A | 07/18/2000 | 08/20/2000 | $150 | $150 | $0 | F - Formal Settlement | ||
| 3. | 02001 | Serious | 23200004 A | 07/18/2000 | 07/24/2000 | $2,700 | $18,000 | $0 | F - Formal Settlement |
Investigation Summary
An apprentice electrician had been working for his employer for 7 months. He was assigned by his supervisor to work on a 277-volt ceiling lighting fixture. He checked the voltage and his testing indicated that the circuit was deenergized. However, as he was pulling out the conductors, he got an electric shock. He asked a supervisor if the circuit had been deenergized, and the supervisor responded that it had been. When he checked the conductors with his voltmeter, he got a no-voltage reading. He pulled out the conductors and, when he cut through them, received another electric shock and a burn on a finger on his right hand. He was hospitalized for his injuries. Employees of another contractor were working at the panelboard supplying the lighting circuit. (Two days earlier, the injured employee had been trimming conductors for a transformer when he received an electric shock. This electric shock had been caused by backfeed on the neutral from another circuit.)
Keywords: BURN, LIGHTING CIRCUIT, E GI IV, ELECTRICAL, FINGER, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR, ELECTRIC SHOCK
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 125493106 | Hospitalized injury | Burn/Scald(Heat) | Electricians' apprentices |