Inspection Detail
Inspection: 1250794 - F E Longstreth Co Inc
Inspection Information - Office: Cincinnati Area Office
Site Address:
F E Longstreth Co Inc
2000 Forrer Blvd
Kettering, OH 45429
Mailing Address:
P O Box 1585, Dayton, OH 45401
Union Status: Union
SIC:1741
NAICS: 0
Inspection Type: Unprog Rel
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 08/09/1984
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 08/09/1984
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360566939 |
Investigation Summary
SEVERAL EMPLOYEES FOR A GENERAL CONSTRUCTION CONTRACTOR WERE CUTTING, CHIPPING, AND REMOVING SECTIONS OF AN EXISTING CONCRETE FLOOR IN A PLANT SO THAT A NEW VIBRATION PAD COULD BE INSTALLED. ONE EMPLOYEE WAS USING A PORTABLE 120-VOLT BATTERY CHARGER TO ASSIST IN STARTING A SCOOT-CRETE POWER BUGGY BEING USED FOR THE REMOVAL OF THE MATERIALS. AFTER BEING USED TO START THE POWER BUGGY, THE BATTERY CHARGER (FOX PRODUCTS COMPANY, MODEL #572N-2) WAS POSITIONED NEXT TO A METAL RAILING. THE EMPLOYEE WAS SECURING THE EQUIPMENT WHEN THE CHARGER DEVELOPED A GROUND FAULT TO ITS CASE. THE BATTERY CHARGER WAS MISSING THE GROUNDING PRONG FROM ITS ATTACHMENT PLUG, AND NO GROUND-FAULT CIRCUIT INTERRUPTER WAS IN USE. WHEN THE EMPLOYEE MADE CONTACT WITH THE CHARGER AND THE METAL RAILING AT THE SAME TIME, HE WAS ELECTROCUTED.
Keywords: ELECTRICAL, EQUIPMENT GROUNDING, ELECTROCUTED, GROUND FAULT, E GI V, BATTERY CHARGER
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 1250794 | Occupation Not Listed |