Inspection Detail
Inspection: 124626573 - Mckay-Dee Hospital
Inspection Information - Office: Utah Division Of Occupational Safety And Health
Site Address:
Mckay-Dee Hospital
3939 Harrison Blvd
Ogden, UT 84403
Mailing Address:
3939 Harrison Blvd, Ogden, UT 84403
Union Status: NonUnion
SIC:8062
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 03/16/1994
Emphasis:
Case Closed: 03/16/1994
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 361532112 |
Investigation Summary
Two electricians were disconnecting some X-ray equipment in a hospital. They pulled a bus trip lug set out of the electrical cabinet to disconnect the cables for the X-ray equipment. (This deenergized the cables so that they could be disconnected safely.) They then removed the flash guard and removed the cables. One of the electricians began to reinstall the lug set without first reinstalling the flash guard. As he was pushing into the cabinet with a large screwdriver, the screwdriver contacted a phase lug and the metal cabinet frame, creating an electrical fault. Both employees sustained burns to their arms and faces as a result of the ensuing electric arc. They were treated at the hospital and released.
Keywords: BURN, E GI II, ELECTRIC ARC, ELECTRICAL, INSULATED TOOL, ELECTRICIAN, ELECTRICAL WORK, ELEC CIRC PART--MISC, ELECTRICAL FAULT
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 124626573 | Non Hospitalized injury | Burn/Scald(Heat) | Electricians | ||
2 | 124626573 | Non Hospitalized injury | Burn/Scald(Heat) | Electricians |