Powered by GoogleTranslate

Inspection Detail

Inspection: 124000068 - Pyromet Industries Inc

Inspection Information - Office: Indiana Department Of Labor

 

Inspection Nr: 124000068
Report ID: 0551800
Date Opened: 02/28/1994

Site Address:
Pyromet Industries Inc
801 W Riggin Road
Muncie, IN 47302

Mailing Address:
123 E. Adams Street, Muncie, IN 47305

Union Status: Union

SIC:3398

NAICS: 0 


Inspection Type: Complaint

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 03/01/1994

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 04/28/1994


Related Activity
Type Activity Nr Safety Health
Accident 361308521
Complaint 77537389 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 4 3 7
Current Violations 3 4 7
Initial Penalty $6,400 $0 $0 $0 $0 $6,400
Current Penalty $2,750 $0 $0 $0 $0 $2,750
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19100147 C01 03/16/1994 06/01/1994 $350 $700 $0 I - Informal Settlement  
2. 01001B Serious 19100147 C04 II 03/16/1994 04/03/1994 $0 $0 $0 -  
3. 01001C Serious 19100147 C06 I 03/16/1994 04/03/1994 $0 $0 $0 -  
4. 01002 Serious 19100147 C07 I 03/16/1994 04/03/1994 $1,875 $2,500 $0 I - Informal Settlement  
5. 01003 Other 19100147 F01 03/16/1994 03/22/1994 $0 $2,500 $0 I - Informal Settlement  
6. 01004 Serious 19100332 B01 03/16/1994 04/25/1994 $525 $700 $0 I - Informal Settlement  
7. 02001 Other 19100303 G01 II 03/16/1994 03/21/1994 $0 $0 $0 -  
8. 02002 Other 19100305 B01 03/16/1994 03/21/1994 $0 $0 $0 -  
9. 02003 Other 19101030 C01 I 03/16/1994 04/03/1994 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 170105522
Event: 02/08/1994
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

A maintenance millwright was working on a mill heat treating furnace. The 480-volt, three-phase electric heating elements were not working. After he diagnosed the problem as the contactor's control coil, he sought assistance from his supervisor. His supervisor instructed him to remove the coil and determine if anything was wrong with it. The millwright opened the disconnect for the contactor, but did not lock it out. He then removed the contactor. Another employee came upon the scene to show something to the supervisor. This employee closed the disconnect and then contacted the leads that had been removed from the contactor. He received an electric shock and was transported to a hospital. He died of his injuries on March 6, 1994.

Keywords: E GI IV, ELECTRICAL, ELECTROCUTED, LOCKOUT, ELEC CIRC PART--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 124000068 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.