Inspection Detail
Inspection: 123815235 - Dobson Powerline Construction
Inspection Information - Office: Ky Labor Cabinet Division Of Osh Compliance
Site Address:
Dobson Powerline Construction
Hwy 70
Willailla, KY 40493
Mailing Address:
7696 Harrodsburg Rd., Nicholasville, KY 40356
Union Status: NonUnion
SIC:1623
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 10/27/1992
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 11/30/1992
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 362000440 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $1,125 | $0 | $0 | $0 | $0 | $1,125 |
| Current Penalty | $1,125 | $0 | $0 | $0 | $0 | $1,125 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19260950 B02 | 11/13/1992 | 11/19/1992 | $1,125 | $1,125 | $0 | - |
Investigation Summary
TWO POWER LINE WORKERS WERE AT A UTILITY POLE, WORKING ON A 7200-VOLT OVERHEAD POWER LINE THAT THEY THOUGHT WAS DEENERGIZED. THEY HAD ISOLATED THE LINE AT A TRANSFORMER AT THE PREVIOUS POLE. THE POWER LINE RAN NORTH AND SOUTH AND WENT OVER A HILL FURTHER TO THE WEST. THE LINE APPEARED TO DEAD END AT AN OLD TRAILER. HOWEVER, THE LINE LOOPED BACK TO THE MAIN LINE 0.25 MILE AWAY. THUS, THE POWER LINE WAS STILL ENERGIZED. ONE OF THE EMPLOYEES WAS WORKING FROM AN AERIAL LIFT, INSTALLING NEW CONDUCTORS. THE OTHER WAS ON THE POLE, REMOVING HARDWARE. THE CONDUCTOR AT THE TOP OF THE POLE WAS CUT, AND IT FELL ONTO THE EMPLOYEE ON THE POLE. HE RECEIVED AN ELECTRIC SHOCK AND SUSTAINED BURNS TO HIS HAND AND SIDE. HE WAS HOSPITALIZED FOR HIS INJURIES.
Keywords: OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, LOCKOUT, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK, UTILITY POLE
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 123815235 | Hospitalized injury | Electric Shock | Electrical power installers and repairers |