Inspection: 123815235 - Dobson Powerline Construction

Inspection Information - Office: Ky Labor Cabinet Division Of Osh Compliance

 

Inspection Nr: 123815235
Report ID: 0452110
Date Opened: 10/09/1992

Site Address:
Dobson Powerline Construction
Hwy 70
Willailla, KY 40493

Mailing Address:
7696 Harrodsburg Rd., Nicholasville, KY 40356

Union Status: NonUnion

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/27/1992

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 11/30/1992


Related Activity
Type Activity Nr Safety Health
Accident 362000440
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $1,125 $0 $0 $0 $0 $1,125
Current Penalty $1,125 $0 $0 $0 $0 $1,125
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260950 B02 11/13/1992 11/19/1992 $1,125 $1,125 $0 -  

Investigation Summary

Investigation Nr: 784421
Event: 10/07/1992
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

TWO POWER LINE WORKERS WERE AT A UTILITY POLE, WORKING ON A 7200-VOLT OVERHEAD POWER LINE THAT THEY THOUGHT WAS DEENERGIZED. THEY HAD ISOLATED THE LINE AT A TRANSFORMER AT THE PREVIOUS POLE. THE POWER LINE RAN NORTH AND SOUTH AND WENT OVER A HILL FURTHER TO THE WEST. THE LINE APPEARED TO DEAD END AT AN OLD TRAILER. HOWEVER, THE LINE LOOPED BACK TO THE MAIN LINE 0.25 MILE AWAY. THUS, THE POWER LINE WAS STILL ENERGIZED. ONE OF THE EMPLOYEES WAS WORKING FROM AN AERIAL LIFT, INSTALLING NEW CONDUCTORS. THE OTHER WAS ON THE POLE, REMOVING HARDWARE. THE CONDUCTOR AT THE TOP OF THE POLE WAS CUT, AND IT FELL ONTO THE EMPLOYEE ON THE POLE. HE RECEIVED AN ELECTRIC SHOCK AND SUSTAINED BURNS TO HIS HAND AND SIDE. HE WAS HOSPITALIZED FOR HIS INJURIES.

Keywords: OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, LOCKOUT, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK, UTILITY POLE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 123815235 Hospitalized injury Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.