Powered by GoogleTranslate

Inspection Detail

Inspection: 123798415 - Bardstown Electric Dept.

Inspection Information - Office: Ky Labor Cabinet Division Of Osh Compliance

 

Inspection Nr: 123798415
Report ID: 0452110
Date Opened: 09/02/1993

Site Address:
Bardstown Electric Dept.
Maiden Alley
Bardstown, KY 40004

Mailing Address:
P. O. Box 368, Bardstown, KY 40004

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: LocalGovt

Safety/Health: Safety

Close Conference: 09/14/1993

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 09/02/1994


Related Activity
Type Activity Nr Safety Health
Accident 361314958
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 5 5
Current Violations 5 5
Initial Penalty $10,000 $0 $0 $0 $0 $10,000
Current Penalty $4,375 $0 $0 $0 $0 $4,375
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260950 C01 I 10/01/1993 10/07/1993 $875 $2,500 $0 10/14/1993 R - Review Commission  
2. 01002 Serious 19260955 E18 II 10/01/1993 10/07/1993 $875 $2,500 $0 10/14/1993 R - Review Commission  
3. 01003A Serious 19260021 B02 10/01/1993 11/12/1993 $875 $2,500 $0 10/14/1993 R - Review Commission  
4. 01003B Serious 19260955 E01 10/01/1993 11/12/1993 $0 $0 $0 10/14/1993 R - Review Commission  
5. 01004 Serious 19260950 E01 II 10/01/1993 11/12/1993 $875 $1,250 $0 10/14/1993 R - Review Commission  
6. 01005A Serious 19101030 C01 I 10/01/1993 11/12/1994 $875 $1,250 $0 10/14/1993 R - Review Commission  
7. 01005B Serious 19101030 D01 10/01/1993 11/12/1993 $0 $0 $0 10/14/1993 R - Review Commission  
8. 01005C Serious 19101030 G02 I 10/01/1993 11/12/1993 $0 $0 $0 10/14/1993 R - Review Commission  

Investigation Summary

Investigation Nr: 170672547
Event: 08/31/1993
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

A power line foreman was working from an aerial lift, restringing an overhead power line. The line on the north side of the utility pole, where he was going to work, was deenergized. The foreman had a bare 2/0 copper conductor with him in the aerial lift bucket when he went up. The conductor was hanging from the bucket and went down along the ground to a spool. He was going to throw the conductor over the crossarm of the pole so that the ground worker could pull it. On his way up, the foreman moved the bucket to the south side of the pole to enable him to fix an insulator on the energized part of the line. He was standing on the conductor hanging from the bucket and was not wearing any electrical protective equipment. He contacted the energized side of the 2400-volt power line and was electrocuted.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 123798415 Fatality Electric Shock Supervisors; electricians & power transm. install.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.