Powered by GoogleTranslate

Inspection Detail

Inspection: 123445793 - Bryant Preserving Company, Inc.

Inspection Information - Office: Little Rock Area Office

 

Inspection Nr: 123445793
Report ID: 0627100
Date Opened: 08/05/1999

Site Address:
Bryant Preserving Company, Inc.
251 Hwy 252 N.
Alma, AR 72921

Mailing Address:
251 Hwy 252 N., Alma, AR 72921

Union Status: NonUnion

SIC:2035

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 09/07/1999

Emphasis:

Case Closed: 01/25/2000


Related Activity
Type Activity Nr Safety Health
Accident 100260587
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 1 4
Current Violations 3 1 4
Initial Penalty $3,750 $0 $0 $300 $0 $4,050
Current Penalty $2,250 $0 $0 $0 $0 $2,250
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100303 G02 I 12/09/1999 01/06/2000 $900 $1,500 $0 I - Informal Settlement  
2. 01002 Serious 19100333 B02 12/09/1999 01/06/2000 $450 $750 $0 I - Informal Settlement  
3. 01003 Serious 19100333 B02 IIC 12/09/1999 01/06/2000 $900 $1,500 $0 I - Informal Settlement  
4. 02001 Other 19100304 A01 12/09/1999 01/06/2000 $0 $300 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 200260693
Event: 08/04/1999
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

A maintenance worker and a helper were replacing a 120-volt, single-phase, dual-capacitor electric motor that had been smoking. The maintenance worker deenergized the circuit and disconnected the wiring to the motor. However, he did not discharge the capacitors or cap the conductors. When the helper began to unbolt the motor from its mounts, he contacted the motor conductors. The capacitors, which combined could store a charge of up to 485 volts, discharged into the helper. The employee was electrocuted.

Keywords: ELECTRIC MOTOR, MAINTENANCE, E GI IV, ELECTRICAL, ELECTROCUTED, CAPACITOR, LOCKOUT, ELEC CIRC PART--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 123445793 Fatality Electric Shock Helpers, mechanics and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.