Powered by GoogleTranslate

Inspection Detail

Inspection: 123272106 - Horizon Communication Inc.

Inspection Information - Office: Houston South Area Office

 

Inspection Nr: 123272106
Report ID: 0626700
Date Opened: 05/06/2000

Site Address:
Horizon Communication Inc.
1900 Blk Fm 3005
Galveston, TX 77504

Mailing Address:
209 Fm 1765, La Marque, TX 77568

Union Status: NonUnion

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 05/08/2000

Emphasis:

Case Closed: 09/26/2000


Related Activity
Type Activity Nr Safety Health
Accident 361139660
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 1 3
Current Violations 1 1
Initial Penalty $5,000 $0 $0 $5,000 $0 $10,000
Current Penalty $0 $0 $0 $2,000 $0 $2,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260095 A 09/21/2000 10/03/2000 $0 $2,500 $0 10/16/2000 J - ALJ Decision Citation has been deleted.
2. 01002 Serious 19260416 A01 09/21/2000 10/03/2000 $0 $2,500 $0 10/16/2000 J - ALJ Decision Citation has been deleted.
3. 02001 Other 19040008 09/21/2000 09/26/2000 $2,000 $5,000 $0 10/16/2000 J - ALJ Decision  

Investigation Summary

Investigation Nr: 14411326
Event: 05/04/2000
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU STRAND

A communications employee was standing in water in a ditch, holding 6-millimeter-diameter, galvanized steel suspension strand. Another employee was working from on a utility pole. The second employee was installing a bracket for the new strand. An existing, corroded bracket on the utility pole broke, allowing the neutral conductor for an overhead power line to contact the 120-volt circuit for a streetlight. The streetlighting conductor then contacted the strand, energizing it. The employee holding the strand, who was not wearing rubber insulating gloves, was electrocuted.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, TELECOM WORK, E TC, ELECTROCUTED, EQUIPMENT FAILURE, SUSPENSION STRAND, COMMUNICATION WORKER

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 123272106 Fatality Electric Shock Telephone line installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close