Inspection Detail
Inspection: 122320567 - Valenti Builders, Inc.
Inspection Information - Office: Chicago North Area Office
Site Address:
Valenti Builders, Inc.
3800 W. Golf Road
Rolling Meadows, IL 60008
Mailing Address:
225 Northfield Road, Northfield, IL 60093
Union Status: Union
SIC:1542
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 02/05/1997
Emphasis:
Case Closed: 02/06/1997
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360360853 |
Investigation Summary
An elevator mechanic was working on electrical boxes on the top of a Dover hydraulic passenger elevator. The elevator was not grounded. An insulation breakdown or failure in the ballast of the elevator's florescent lighting fixture energized the entire elevator car. (The ballast was in metal-to-metal contact with the ceiling of the car.) The mechanic was electrocuted.
Keywords: BALLAST--LIGHTING, ELEC INSULATION, E GI IV, ELECTRICAL, GROUND FAULT, EQUIPMENT GROUNDING, ELEVATOR, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT