Inspection Detail
Inspection: 122186026 - William C. Jennings Management Co.
Inspection Information - Office: Dallas Area Office
Site Address:
William C. Jennings Management Co.
4900 Via Ventura
Mesquite, TX 75150
Mailing Address:
800 8th Avenue, Suite 340, Ft. Worth, TX 76104
Union Status: NonUnion
SIC:6513
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: Y
Ownership: Private
Safety/Health: Safety
Close Conference: 09/23/1998
Emphasis:
Case Closed: 06/25/1999
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360377444 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 2 | 2 | ||||
| Current Violations | 2 | 2 | ||||
| Initial Penalty | $3,000 | $0 | $0 | $0 | $0 | $3,000 |
| Current Penalty | $2,100 | $0 | $0 | $0 | $0 | $2,100 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19100332 B01 | 10/29/1998 | 12/17/1998 | $1,050 | $1,500 | $0 | 11/18/1998 | F - Formal Settlement | |
| 2. | 01002 | Serious | 19100333 C02 | 10/29/1998 | 12/17/1998 | $1,050 | $1,500 | $0 | 11/18/1998 | F - Formal Settlement |
Investigation Summary
A conductor for a compressor fan motor had been incorrectly connected. It should have been connected to a relay that connected it to a step-down transformer to lower the voltage from 288 volts to 24 volts. However, it had apparently been connected to a 288-volt source. The overvoltage had melted the scotch locks on the external wiring for a thermostat, exposing energized conductors. The employee who had wired the improper connection had inadequate electrical training and no supervision from a qualified person. An apartment maintenance employee touched the ends of the thermostat conductors as he was repairing the air-conditioning unit and was electrocuted. (It was not clear from the original form whether the maintenance employee was the one who miswired the unit.)
Keywords: REPAIR, E GI IV, ELECTRICAL, AIR CONDITIONER, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, UNTRAINED
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 122186026 | Fatality | Electric Shock | Janitors and cleaners |