Powered by GoogleTranslate

Inspection Detail

Inspection: 122186026 - William C. Jennings Management Co.

Inspection Information - Office: Dallas Area Office

 

Inspection Nr: 122186026
Report ID: 0626300
Date Opened: 06/25/1998

Site Address:
William C. Jennings Management Co.
4900 Via Ventura
Mesquite, TX 75150

Mailing Address:
800 8th Avenue, Suite 340, Ft. Worth, TX 76104

Union Status: NonUnion

SIC:6513

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 09/23/1998

Emphasis:

Case Closed: 06/25/1999


Related Activity
Type Activity Nr Safety Health
Accident 360377444
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $3,000 $0 $0 $0 $0 $3,000
Current Penalty $2,100 $0 $0 $0 $0 $2,100
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100332 B01 10/29/1998 12/17/1998 $1,050 $1,500 $0 11/18/1998 F - Formal Settlement  
2. 01002 Serious 19100333 C02 10/29/1998 12/17/1998 $1,050 $1,500 $0 11/18/1998 F - Formal Settlement  

Investigation Summary

Investigation Nr: 200780393
Event: 06/23/1998
electric shock - direct contact with energized conductor

A conductor for a compressor fan motor had been incorrectly connected. It should have been connected to a relay that connected it to a step-down transformer to lower the voltage from 288 volts to 24 volts. However, it had apparently been connected to a 288-volt source. The overvoltage had melted the scotch locks on the external wiring for a thermostat, exposing energized conductors. The employee who had wired the improper connection had inadequate electrical training and no supervision from a qualified person. An apartment maintenance employee touched the ends of the thermostat conductors as he was repairing the air-conditioning unit and was electrocuted. (It was not clear from the original form whether the maintenance employee was the one who miswired the unit.)

Keywords: REPAIR, E GI IV, ELECTRICAL, AIR CONDITIONER, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, UNTRAINED

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 122186026 Fatality Electric Shock Janitors and cleaners
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.