Powered by GoogleTranslate

Inspection Detail

Inspection: 122175870 - Woodbine Electric Service, Inc.

Inspection Information - Office: Dallas Area Office

 

Inspection Nr: 122175870
Report ID: 0626300
Date Opened: 10/21/1997

Site Address:
Woodbine Electric Service, Inc.
Hwy 31 & Shell Pipe Line
Kilgore, TX 75662

Mailing Address:
Peavine Rd & 135 N, Kilgore, TX 75662

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 01/08/1998

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 08/19/1998


Related Activity
Type Activity Nr Safety Health
Accident 100780154
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $1,500 $0 $0 $0 $0 $1,500
Current Penalty $0 $0 $0 $500 $0 $500
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 19100333 C03 IIA 01/09/1998 01/15/1998 $500 $1,500 $0 02/05/1998 F - Formal Settlement  

Investigation Summary

Investigation Nr: 200780294
Event: 10/13/1997
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

An electrical contractor received a service call from a refinery. There was an electrical problem at one of their crude oil dumping stations. The drivers had complained of seeing sparks come from the overhead power line on the utility pole next to the dumping station. The 480-volt overhead power line was a secondary three-phase distribution line that ended downstream from the dumping station. The contractor sent two journeyman electricians to respond to the call. Upon reaching the problem site with a plant official, the electricians found an aluminum squeeze-on connection than had worked itself loose. The connection was for a jumper. One of the electricians decided to use a different type of connector. The plant official told the electricians that the line could be deenergized if necessary. After two trips to the parts warehouse, the electricians had the correct size connector to effect the repair. However, when they returned, the plant official was not around. One of the electricians ascended in an aerial lift, cut the energized jumper, put the connector on the deenergized side of the jumper, and started to connect it to the energized line. He received an electric shock, which rendered him unconscious, when he touched the deenergized jumper and the energized line at the same time. His coworker lowered him and administered cardio-pulmonary resuscitation to no avail. The employee was electrocuted. (He had burn marks on both hands and reddish skin abrasions or burns on his chest.) The Sky Jacker aerial lift in which he had been working was insulated and had recently been serviced.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, CPR, ELECTRICIAN, ELECTROCUTED, E PTD, ELEC UTILITY WORK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 122175870 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.