Powered by GoogleTranslate

Inspection Detail

Inspection: 122041973 - Wisconsin Electric Power Company

Inspection Information - Office: Milwaukee Area Office

 

Inspection Nr: 122041973
Report ID: 0523400
Date Opened: 07/22/1994

Site Address:
Wisconsin Electric Power Company
9600 West Forest Home Avenue
Milwaukee, WI 53130

Mailing Address:
P.O. Box 2046, Milwaukee, WI 53201

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/01/1994

Emphasis:

Case Closed: 09/06/1994


Related Activity
Type Activity Nr Safety Health
Accident 360407035

Investigation Summary

Investigation Nr: 14367023
Event: 07/22/1994
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

An underground transformer supplying service for a residential complex had been repaired. A troubleshooter with 42 years of experience was dispatched to reenergize the line supplying the transformer. The employee was working from a utility pole at the primary (4800-volt) level. There were two parallel lines, an east and a west, descending the pole at this point. Only the west line was deenergized; the east line remained energized. The employee was to remove the three grounding jumpers from the pothead stirrups located on the lower crossarm and then from the grounding bracket on the other side of this crossarm. Then he was to reenergize the west line. The employee positioned himself on the south side of the pole--he was facing north with the energized east potheads to his right. The horizontal distance between the grounding bracket and the nearest energized pothead was about 400 millimeters. The employee had removed the three grounding jumpers from the west potheads and had started to remove the jumpers from the grounding bracket. He was using metal pliers and leather wristlet gloves for this purpose. (He was not wearing rubber insulating gloves, nor were the energized east potheads or lines covered with rubber insulating equipment.) The employee contacted an energized east pothead with his right forearm while his right hand was touching the grounding bracket. The employee was electrocuted.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, UTILITY POLE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 122041973 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.